Honeywell AQ25A Series Technical Reference Booklet page 21

Programmable boiler control panels
Hide thumbs Also See for AQ25A Series:
Table of Contents

Advertisement

When you finish setting the DIP switches for all the Zoning
Modules, replace the front cover of the AQ25A Control Panel
and the cover of each Expansion Zoning Panel.
Table 2. AQ15540B Zoning Module (Pump Zoning Module) DIP Switch Arrangement.
DIP
Switch
1
Zone Address: The positions of these 4 DIP switches define the unique address for
2
each zone on the AQUATROL network. For each group of 4 zones, there can be only
3
one DIP switch in the right hand (ON) position.
4
The correct DIP switch settings for each zone module are:
• First Zone (1-4) Module:
• Second Zone (5-8) Module: 2 = ON position; 1, 3, and 4 = OFF position
• Third Zone (9-12) Module:
• Fourth Zone (13-16) Module: 4 = ON position; 1, 2, and 3 = OFF position
• If set to SYNC, zone synchronization is enabled.
5
• If set to NOT, zone synchronization is disabled.
• If zone valves are normally closed (N.C.), set the NC/NO DIP switch to the OFF
position.
• If zone valves are normally open (N.O.), set the NC/NO DIP switch to the ON
6
position.
• If set to Group (ON position), the AUX Pump contacts on the Control Module are
switched when any of the zones on this Zoning Module are active.
• If set to - (OFF position), the AUX Pump contacts are not affected by activity on
7
these zones.
• If set to 2-stage (ON position), then 2-stage operation is activated on thermostat
inputs. The zoning module operates as two 2-stage zones.
8
• If set to 1-stage (OFF position), then operates as four 1-stage zones.
AQ25A SERIES PROGRAMMABLE BOILER CONTROL PANELS
NOTE: The snap-on DIP switch covers are designed so they
Switch Description
1 = ON position; 2, 3, and 4 = OFF position
3 = ON position; 1, 2, and 4 = OFF position
15
cannot be removed (exposing the DIP switches)
when the front cover of the AQ25A Control Panel is in
place.
Label and Factory Settings
AQ15540B
Diagnostic
Diagnostic
Test
Test
M27696
M23720A
69-2119—02

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

Table of Contents