Honeywell AQ25A Series Technical Reference Booklet page 33

Programmable boiler control panels
Hide thumbs Also See for AQ25A Series:
Table of Contents

Advertisement

Menu Option
EDIT SINGLE ZONE
FLOOR TEMP
FLOOR SETPT
SETBACK
SETPOINT MAX
SETPOINT MIN
SETPOINT VACANCY
HEAT
KEYBOARD
EDIT SINGLE ZONE
ZONE #A-X
ROOM TEMP
FLOOR TEMP
SETPOINT
H/C STATUS
SETBACK
SETPOINT MAX
SETPOINT MIN
Table 5. User Menu. (Continued)
Factory
Range
Default
Floor Style — Selecting this menu item displays the following options:
32°F to 158°F
(0ºC to 70°C)
41°F to 100°F
70°F
(5ºC to 38 °C)
(21°C)
0°F to 16°F
7°F
(0ºC to 9°C)
(4°C)
41°F to 100°F
100°F
(5ºC to 38 °C)
(38°C)
41°F to 100°F
41°F
(5ºC to 38 °C)
(5°C)
41°F to 100°F
41°F
(5ºC to 38 °C)
(5°C)
LOCK or
UNLOCK
UNLOCK
Ambient/Floor Style — Selecting this menu item displays the following options:
A-1 to A-16
A-1
...
D-1 to D-16
32°F to 158°F
(0ºC to 70°C)
32°F to 158°F
(0ºC to 70°C)
Between
70°F
SETPOINT MIN
(21°C)
and
SETPOINT MAX
HEAT or
COOL
0°F to 16°F
7°F
(0ºC to 9°C)
(4°C)
41°F to 100°F
100°F
(5ºC to 38 °C)
(38°C)
41°F to 100°F
41°F
(5ºC to 38 °C)
(5°C)
AQ25A SERIES PROGRAMMABLE BOILER CONTROL PANELS
n/a
Display only. This is the temperature measured by the floor
temperature sensor.
This menu option displays only when the AQ1000
thermostat is set to FLOOR ONLY mode.
Amount of temperature (number of degrees) setback from
occupied to unoccupied modes for this zone.
Maximum setpoint temperature allowed for this zone's
thermostat. The SETPOINT MAX cannot be set below the
SETPOINT MIN setting.
Minimum setpoint temperature allowed for this zone's
thermostat. The SETPOINT MIN cannot be set above the
SETPOINT MAX setting.
Target HEATING temperature for the zone when system is
in VACANCY mode.
Controls the zone thermostat's keyboard.
• If set to LOCK, settings cannot be changed at that
zone's thermostat.
• If set to UNLOCK, the thermostat's settings can be
changed within the SETPOINT MAX and SETPOINT
MIN limits.
Each zone on the AQUATROL network has a unique
identity (address). This address consists of a Control
Module ID and the Zone related to that controller.
• Module ID: The Boiler Controller is A, and the 1st
through 3rd Add-A-Temperature Expansion Control
Modules (i.e., AQ25400B) are B, C, and D.
• Zone: From 1 to 16 for each Module ID.
A total of four controllers (one Boiler Control Module and
up to three Add-A-Temperature Expansion Control
Modules) each having 16 associated zones can be
connected on the AQUATROL network. The AQ25A
Control Panel itself can control one Boiler loop water
temperature and one secondary loop water temperature.
n/a
Display only. This is the temperature measured by the
zone thermostat.
n/a
Display only – Temperature measured by the floor
temperature sensor.
Target temperature set for the zone.
n/a
Display only – Status is received from each zone
thermostat every 10 seconds.
Amount of temperature (number of degrees) setback from
occupied to unoccupied modes for this zone.
Maximum setpoint temperature allowed for this zone's
thermostat. The SETPOINT MAX cannot be set below the
SETPOINT MIN setting.
Minimum setpoint temperature allowed for this zone's
thermostat. The SETPOINT MIN cannot be set above the
SETPOINT MAX setting.
27