Menu Option
EDIT SINGLE ZONE
a
FLOOR LIMIT HI
a
FLOOR LIMIT LO
SETPOINT VACANCY
HEAT
SETPOINT VACANCY
COOL
CHANGEOVER
KEYBOARD
PROGRAM SETTINGS
MODE
EDIT ALL DAYS
EDIT DAILY
Table 5. User Menu. (Continued)
Factory
Range
Default
Ambient/Floor Style (continued)
41°F to 100°F
100°F
(5ºC to 38 °C)
(38°C)
41°F to 100°F
41°F
(5ºC to 38 °C)
(5°C)
41°F to 100°F
41°F
(5ºC to 38 °C)
(5°C)
41°F to 100°F
100°F
(5°C to 38°C)
(38°C)
2°F to 9ºF
2°F
(1ºC to 5ºC)
(1ºC)
LOCK or
UNLOCK
UNLOCK
Displays, and allows for editing of, the temperature setpoints for each of the four time
periods (or programs) within a 24-hour period (WAKE, LEAVE, RETRN (return), and SLEEP).
AUTO,
AUTO
OCC, or
UNOCC
ALL WAKE,
WAKE=6:00AM
ALL LEAVE,
LEAVE=8:00AM
ALL RETRN, or
RETRN=6:00PM
ALL SLEEP
SLEEP=10:00PM
WAKE,
WAKE=6:00AM
LEAVE,
LEAVE=8:00AM
RETRN, or
RETRN=6:00PM
SLEEP
SLEEP=10:00PM
AQ252 Universal Injection/Mixing Boiler Reset Control Panels
Maximum floor temperature allowed for a given zone that is
controlled by a floor / slab sensor connected to that zone's
AQ1000 thermostat. At floor maximum, the zone
equipment is turned off. The FLOOR MAX cannot be set
below the FLOOR MIN setting.
Minimum floor temperature allowed for a given zone that is
controlled by a floor / slab sensor connected to that zone's
AQ1000 thermostat. At Floor MIN, the zone equip is
energized. The FLOOR MIN cannot be set above the
FLOOR MAX setting.
Target HEATING temperature for the zone when system is
in VACANCY mode.
Target COOLING temperature for the zone when system is
in VACANCY mode.
Only displays when cooling is enabled for that zone.
Temperature deadband that determines the changeover
from heating to cooling and from cooling to heating:
• The thermostat switches from heating to cooling mode
when the indoor temperature is higher than the setpoint
by more than the changeover band setting for 15
minutes.
• The thermostat switches from cooling to heating mode
when the indoor temperature is lower than the setpoint
by more than the changeover band setting for 15
minutes.
Controls the zone thermostat's keyboard.
• If set to LOCK, settings cannot be changed at that
zone's thermostat.
• If set to UNLOCK, the floor thermostat's settings can be
changed within the FLOOR MAX and FLOOR MIN
limits.
• AUTO = Automatically follow the four time periods (or
programs) within a 24 hour period, as set up in the Edit
All Days or Edit Daily sub-menus. The four programs
are WAKE, LEAVE, RETRN (return), and SLEEP.
• OCC = Observe the program settings only for WAKE
and RETRN (return).
• UNOCC = Observe the program settings only for
LEAVE and SLEEP.
Allows Installer to set the WAKE, LEAVE, RETRN (return),
and SLEEP times once, and apply the settings to all 7
days.
NOTE: The programs will be copied to the individual days
only when the COPY TO ALL DAYS option is
selected.
Allows Installer to set the WAKE, LEAVE, RETRN (return),
and SLEEP times for all 7 days individually.
29
Description
69-1986—02