Honeywell AQ25A Series Technical Reference Booklet page 22

Programmable boiler control panels
Hide thumbs Also See for AQ25A Series:
Table of Contents

Advertisement

AQ25A SERIES PROGRAMMABLE BOILER CONTROL PANELS
AQ25A – System Programming
This section describes how to navigate the user interface using
the keypad and LCD display, and how to program the AQ25A
Control Panel, which begins on page 17.
Keypad
The AQ25A User Interface consists of an LCD screen (16
characters by 3 rows) and a 7-button keypad for navigating the
menus, as illustrated in Fig. 22. Fig. 21 provides an isolated
view of the keypad.
Fig. 21. AQ25A keypad.
Menu
Press this button to access the User Menu. When
pressed while in a sub-menu, the sub-menu's
values are saved before going up one level in the
current menu.
Home
Press this button to leave the User or Installer Menu
and return to the Home Page display screen.
OK
Press this button to enter a sub-menu of the active
menu item. A menu item is active when the indicator
arrow (←) is positioned beside the item.
STATUS OF SYSTEM DEMANDS
- CALL FOR HEAT
- CALL FOR DHW
- SIGNAL ON AUXILIARY INPUT
GRAPHIC SHOWING
THE PERCENTAGE
OF THE BOILER'S
HEATING CAPACITY
AT WHICH IT'S
OPERATING; ARROWS
ABOVE AND BELOW
THE BAR SHOW THE
TREND OF THE
BOILER'S
TEMPERATURE
(UP OR DOWN)
STATUS OF LINE VOLTAGE OUTPUTS
- PRIMARY (BOILER) HEAT
- DHW PUMP
- SECONDARY PUMP
- AUXILIARY "PUMP" OUTPUT
69-2119—02
and v
^
– and +
LCD Display
The LCD on the AQ25A Control Panel is used to:
M23538
The layout of the display is logical and simple to navigate. The
information displays so that the installer can see at a glance
the system's operating temperatures as well as the status of
the system equipment such as a Call for heat, DHW pump On,
Boiler T-T terminals energized, etc. In addition, all system
information displays in simple, straightforward English for quick
system diagnosis. Fig. 22 illustrates the layout and features of
the LCD display panel and keypad.
STATUS OF SYSTEM OUTPUTS
- AUXILIARY OUTPUT ACTIVE
- BOILER T-T OUTPUT ACTIVE
:
:
DOWN ARROW, IF DISPLAYED,
GRAPHIC SHOWING THE DEGREE OF
INDICATES THAT OTHER MENU ITEMS
MIXING IN THE SECONDARY LOOP:
EXIST BELOW AND CAN BE VIEWED
# OF BARS INCREASES AS A) THE
BY SCROLLING DOWN WITH
INJECTION PUMP SPEED INCREASES,
THE
B) THE VOLTAGE OF THE MODULATING
VALVE SIGNAL INCREASES OR C) THE
ACTUAL MIX TEMPERATURE APPROACHES
THE MAXIMUM MIX TEMPERATURE
Fig. 22. LCD display and keypad layout.
16
Press these buttons to scroll up/down in the menu
items. Pressing one of these buttons automatically
saves your current selection, exits the edit mode,
and moves to the previous or next menu item.
Press these buttons to decrease/increase the value
of a selected menu item, or to scroll through a list of
pre-defined options.
- If the menu item being modified is a number, the
displayed value will decrease/increase by pressing
these buttons. When holding the – or + button for
more than a second, the values automatically
decrease/increase at a faster pace, similar to setting
the time on a digital clock radio
- If the menu item is an option, pressing these
buttons scrolls through the list of available options
one at a time.
— Monitor system status and performance.
— Select and/or modify control settings for the hydronic
system.
— Diagnose and troubleshoot system problems.
DISPLAY AREA SHOWING
SYSTEM STATUS AND MENU
OPTIONS AND SELECTIONS
MADE
ARROW INDICATES
THE CURRENTLY SELECTED
"ACTIVE" MENU ITEM.
BUTTON.
.
UP ARROW, IF DISPLAYED,
INDICATES THAT OTHER MENU
ITEMS EXIST ABOVE AND CAN
BE VIEWED BY SCROLLING
UP WITH THE
BUTTON.
M27698

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

Table of Contents