Honeywell AQ25A Series Technical Reference Booklet page 41

Programmable boiler control panels
Hide thumbs Also See for AQ25A Series:
Table of Contents

Advertisement

Menu Option
TEST OUTPUTS
Tests the individual system outputs to ensure correct operation.
BOILER PUMP ON / OFF
AUX PUMP
ON / OFF
(close / open)
DHW PUMP
ON / OFF
BOILER T-T
ON / OFF
(close / open)
AUX OUT
ON / OFF
(close / open)
10V MOD
0V to 10V
TEST SENSORS
Tests the supply, return and outdoor temperature sensors to ensure correct operation
OUTDOOR
- -
LO
-58° to 212°F (-50° to 100°C)
HI
BOILER
- -
LO
-49° to 257°F (-45° to 125°C)
HI
RETURN
- -
LO
-49° to 257°F (-45° to 125°C)
HI
DHW
- -
LO
-49° to 257°F (-45° to 125°C)
HI
Table 7. Installer Menu – Test and Purge.
TEST and PURGE
Factory
Range
Default
OFF
OFF
(open)
OFF
OFF
(open)
OFF
(open)
0V
n/a
n/a
n/a
n/a
35
AQ25A SERIES PROGRAMMABLE BOILER CONTROL PANELS
Energizes / de-energizes the line voltage terminals marked
Boiler when switched to ON / OFF respectively.
Closes / opens the line voltage rated dry contacts marked
Aux. when switched to ON / OFF, respectively.
Energizes / de-energizes the line voltage rated terminals
marked DHW when switched to ON / OFF respectively.
Closes / opens the low voltage rated dry contacts (terminals
17 and 18) marked Boiler T-T when switched to ON / OFF
respectively.
Closes / opens the low voltage rated dry contacts (terminals
19 and 20) marked Aux. Out. when switched to ON / OFF
respectively.
Produces voltage on the 10 Vdc low voltage terminals (15
and 16), according to the setting chosen (0V to 10V), in
increments of 1V.
Displays the temperature measured by the outdoor sensor.
"- -" means sensor is disconnected
LO means temperature reading is below -55°F (-50°C)
HI means temperature reading is above 212°F (100°C)
Displays the temperature measured by the boiler supply
sensor.
"- -" means sensor is disconnected
LO means temperature reading is below -49°F (-45°C)
HI means temperature reading is above 257°F (125°C)
Displays the temperature measured by the Return/DHW
sensor.
"- -" means sensor is disconnected
LO means temperature reading is below -49°F (-45°C)
HI means temperature reading is above 257°F (125°C)
Does not display when the RETURN/DHW sensor is
configured as a DHW sensor.
Displays the temperature measured by the sensor
configured for DHW (the sensor wired to the Return/DHW
terminals 5 and 6).
"- -" means sensor is disconnected
LO means temperature reading is below -49°F (-45°C)
HI means temperature reading is above 257°F (125°C)
Displays only when the sensor is configured as a DHW
sensor.
Description
69-2119—02