Menu Option
Settings which the AQ25A uses to control the system based on input to the AUX. IN terminals or
AUXILIARY I/O
to control the activation of the AUX.OUT and AUX.PUMP outputs.
AUX.IN
SETBACK / VACANCY /
(optional)
EM. SHUT / NONE
AUX.OUT
BOILER / SETBACK /
(optional)
ZONE OP. / ALARM /
AUX.IN / DHW IN / HEAT IN /
HT DMND / COOL / NONE
AUX.PUMP
BOILER / GROUP / OCC /
(optional)
BYPASS / FAN / NONE /
AUX.IN / DHW IN / HEAT IN /
HT DMND
A/C SETTINGS
Central A/C – Available only if no AQ158 controller is present on the network.
CYCLES/HOUR
2 / 3 / 4 / 5 / 6
MIN.OFF TIME
2 to 10 (minutes)
C.W.S.D.
- -
32°F to 100°F (0°C to 38°C)
FAN MODE
AUTO / ON
Table 6. Installer Menu – Equipment Setup. (Continued)
EQUIPMENT SETUP
Factory
Range
Default
SETBACK
BOILER
BOILER
4
5M
65°F
(18°C)
AUTO
33
AQ25A SERIES PROGRAMMABLE BOILER CONTROL PANELS
Based on the setting chosen, the AQ25A sets the system
in one of 3 different levels of setback for as long as the
Aux. In terminals are shorted. Refer to instruction sheet for
AQ1000 thermostat (69- 2005EF) for setting the Vacancy
(Freeze Protection) temperature setpoint.
Based on the setting chosen, the AQ25A closes the AUX.
Out dry contact terminals when:
• BOILER: The boiler pump energizes.
• SETBACK: The system program is in setback mode
(either SLEEP or LEAVE).
• ZONE OP.: The end switch of a zone valve connected
to a Zoning Module closes or a zone pump energizes.
• ALARM: An alarm is detected on the system.
• AUX.IN, DHW IN, HEAT IN, or HEAT DMND: An input
signal is detected on the respective terminals.
• COOL: There is a call for cooling from a programmable
AQ1000 thermostat. The COOL option is available only
if central A/C is present; see the "A/C SETTINGS" and
"A/C EQUIP CONFIG" menu options in this table.
• NONE: indicates that the Aux Out terminals are not
used.
Based on the setting chosen, the AQ25A closes the Aux.
Pump dry contacts when:
• BOILER: The boiler pump energizes.
• GROUP: Any of the thermostats in a Group of zones
(identified by the Zoning Module's DIP switch #7 [AUX]
being switched to YES) energize.
• OCC: The system program is in Occupied mode (either
WAKE or RETRN).
• BYPASS: The boiler return sensor measures a water
temperature less than the value defined for the
EQUIPMENT SETUP > BOILER SETTING > MIN
RETURN setting.
• FAN: There is a call for cooling from a programmable
AQ1000 thermostat. The FAN option is available only if
central A/C is present; see the "A/C SETTINGS" and
"A/C EQUIP CONFIG" menu options in this table
• AUX.IN, DHW IN, HEAT IN, or HEAT DMND: An input
signal is detected on the respective terminals.
• NONE: indicates that the Aux Pump terminals are not
used.
The maximum number of times the controller will permit
the central A/C to cycle in each hour.
The length of time that must elapse after the AC
compressor shuts off before the Aux. Out relay is permitted
to close, to energize the compressor again.
The temperature at which cold weather shutdown is
activated.
• "- -" means Off (not used).
Selects whether or not the fan serving the A/C system
operates constantly (ON) or operates only when there is a
call for cooling (AUTO).
FAN MODE displays only if the FAN option is selected for
AUX.PUMP. See "AUX.PUMP" menu option in this table.
Description
69-2119—02