3.6.5.4.4 AC Loss Delay
The reporting of a loss of AC power to a central station can be delayed by
programming the length of the desired delay. Press 1 while viewing Timer Screen
#2 to display the following:
AC LOSS DELAY
1=NO DELAY
2=ENTER DELAY
AC Loss Delay Screen #1
Pressing 1 while viewing AC Loss Delay Screen #1 will program the FACP to
transmit an AC Loss report immediately to the central station.
Pressing 2 while viewing AC Loss Delay Screen #1 will display the following:
AC LOSS DELAY
RANGE 00-23
AC Loss Delay Screen #2
A flashing cursor will appear in the lower left corner of the display. Type the two
digit AC loss reporting delay in hours (00 to 23 hour delay). When the second digit
is entered, the display will return to AC Loss Delay Screen #1.
Important: For Central Station applications, AC Loss Reporting Delay must be set
to a delay value ranging from 06 to 12 hours. For Remote Station applications, AC
Loss Reporting Delay must be set to a delay value ranging from 15 to 23 hours.
Note: AC Loss Delay also applies to any programmable output relay programmed
for 'AC Loss.'

3.6.5.5 NAC (Notification Appliance Circuit)

The options for the NACs on the control panel main circuit board can be configure
by pressing 2 while viewing System Setup Screen #2. The following screens will
be displayed:
1=NAC 1
2=NAC 2
The Notification Appliance Circuits can be configured independently by pressing 1
for NAC 1, 2 for NAC 2, 3 for NAC 3 or 4 for NAC 4.
Note that 3=NAC 3 and 4=NAC 4 will be displayed, and can be programmed,
regardless of how the NACKEY card is installed. Their programming, however, will
have no effect if the NACKEY card is installed for Class A operation.
Master Programming Level
NACS
3=NAC 3
4=NAC 4
NAC Selection Screen
MS-9200UDLS PN 52750:A 11/04/05