Master Programming Level
EDIT CONTROL
1=ENABLED
2=TYPE
3=SILENCEABLE
Edit Control Screen #2
MS-9200UDLS PN 52750:A 11/04/05
To change the programming for the displayed module, press the keyboard down
arrow key to view the following Edit Control screens:
EDIT CONTROL
1=ENABLED
2=TYPE
3=SILENCEABLE
Edit Control Screen #2
EDIT CONTROL
1=WALKTEST
2=ZONE ASSIGNMENT
00 ** ** ** **
Edit Control Screen #3
EDIT CONTROL
1=NOUN/ADJECTIVE
2=DESCRIPTION
********************
Edit Control Screen #4
Enable/Disable Module
To Enable or Disable the control module, press the 1 key while viewing the Edit
Control Screen #2. Each press of the key will toggle the screen between Enabled
Yes and Enabled No. If Enabled No is selected, the module will not be polled by the
control panel, preventing the module from activating its output devices. The control
panel will indicate a system trouble condition and the Disable LED will turn on if
any devices are disabled.
YES
CONTROL
YES
YES
Programming
69