Downloading Initiated at a Service Terminal

6.2 Downloading Initiated at a Service Terminal
MS-9200UDLS PN 52750:A 11/04/05
Before initiating the download procedure, make certain that the control panel is:
In Normal Mode
Central Station communications are off
The communicator is in the standby state (red phone line active LEDs are off
and Kissoff LEDs are off)
Once the control panel accepts/answers an incoming call, the panel will:
1. Establish basic modem connection
2. Verify secret code and panel identification number
3. Verify callback vs. no callback request from the service terminal. If callback is
requested, steps 4 through 9 will occur. If no callback is requested, only steps 8
and 9 will occur
4. Identify the Service Terminal location
5. Hang-up/disconnect call
6. Call the Central Station(s) and transmit a request for upload/download message
(if programmed to do so). If this message is accepted, the control panel will
proceed to the next step
7. Return call to Service Terminal
8. After security clearance, begin downloading
9. Upon completion of download, call Central Station(s) back and report either a
successful download or failed upload/download message (if programmed to do
so)
Remote Site Upload/Download
161