Master Programming Level
CENTRAL STATION
1=TEST TIME INT
2=ACCOUNT CODE
3=24HR TST TIME
Primary/Secondary Screen #1
CENTRAL STATION
1=PHONE NUMBER
Primary/Secondary Screen #2
MS-9200UDLS PN 52750:A 11/04/05
24 Hour Test Time
Pressing 3 while viewing Primary/Secondary Screen #1 will cause the following
screen to be displayed:
24 HOUR TEST TIME
RANGE 0000-2359
24 Hour Test Time Screen
Use the 24 Hour Test Time screen to program the time that the DACT will transmit
the 24 Hour Test to the Central Station. A flashing cursor will appear in the lower
left corner of the screen. Enter a four digit number representing the test time using
military time (0000 = midnight and 2359 = 11:59PM).
Phone Number
Pressing 1 while viewing Primary/Secondary Screen #2 will cause the following
screen to be displayed:
PHONE NUMBER
20 NUMBERS MAXIMUM
Phone Number Screen
The Phone Number screen is used to enter the Central Station phone number that
the DACT will be contacting. A maximum of 20 characters can be entered with
valid entries being 0 - 9 and A - F where A = *, B = #, C = look for secondary dial
tone for up to 2 seconds (then dial anyway), D = 3 second pause, E = 5 second pause
and F = end of phone number (must be entered at end of phone number).
A flashing cursor will appear in the lower left corner of the screen. Enter the first
digit then press the right arrow key to move the cursor to the right one position.
Enter the second digit and repeat the process until all digits are entered. Press the
Enter key to store the phone number in memory.
Enter the digits as you would like the number to be dialed. For example, if it's
necessary to dial 9 before dialing a number outside the building, you may wish to
pause after dialing 9. Enter 9 followed by D for a three second pause or E for a five
second pause then the phone number followed by an F to indicate the end of the
number.
Programming