Programming
6.6

Panel Programming Options

All customized programming options for the 5600 control panel are described in this section
and are available to be edited using the embedded web server of the control panel.
6.6.1

System Options

6.6.1.1 Synchronized Strobes Active When Horns Silenced

The default configuration for this option is No. If set to Yes, strobes will remain on when
horns are silenced until a panel reset is issued.

6.6.1.2 Silence/Reset Inhibit Enabled

The default configuration for this option is NO. If set to Yes, Pressing either Reset or Silence
Buttons will be ignored for the duration of the delay (set to 30 seconds). The inhibit feature
delay is only active for the first alarm/supervisory signal.

6.6.1.3 Water Flow Delay

The water flow delay is a debounce time that is generally used to help reduce false alarms
during brief periods of water pressure fluctuation in a water riser. The default setting is 1
second which is the minimum debounce time. You can set the water flow delay within the
range 1-90 seconds.

6.6.1.4 Installer Code (User ID)

This is the password used to lock the list of SLC devices found during the JumpStart auto
learn process. It is defaulted to 123456 and can be changed to any 4 to 8 digit number.

6.6.1.5 Alarm Verification Time

Alarm verification is an optional false alarm prevention feature for smoke detectors that
verifies an alarm condition by resetting the smoke detector. The alarm verification time can be
set within the range of 1-250 seconds. For UL 864 installations this option must be greater
than 59 seconds. The default setting is 60 seconds.

6.6.1.6 Auto Test

Enter the hour/minutes (in 24 hour format) that you desire the control panel to send the
automatic test report.

6.6.1.7 Low AC Report Delay

This option determines the number of delay hours before a loss of AC is reported to the
central station. It is defaulted to 3 hours and must be within the range 0-30 hours. For U.L.
864 installation this option must be set within the range 1-3 hours.