Master Programming Level
CENTRAL STATION
1=EVENT CODES
Primary/Secondary Screen #4
MS-9200UDLS PN 52750:A 11/04/05
The Communication Format is determined by the type of receiver that the DACT is
transmitting to. Consult your Central Station for proper selection or consult our
factory representatives. For any format chosen, the control panel automatically
programs all of the event codes.
Select the Communication Format by pressing the corresponding number key while
viewing the appropriate Comm Format screen. The following table describes each
format:
Table 3.1 Communication Formats
Screen Selection
ADEMCO EXPRESS 4P1
ADEMCO EXPRESS 4P2
3P1S C18 A23
3P1E C18 A23
3P1S C19 A14
3P1E C19 A14
4P1S C18 A23
4P1E C18 A23
4P1S C19 A14
4P1E C19 A14
4P2S C18 A23
4P2E C18 A23
4P2S C19 A14
4P2E C19 A14
ADEMCO CONTACT ID
Event Codes
Pressing 1 while viewing Primary/Secondary Screen #4 will cause the following
screen to be displayed:
EVENT CODES
1=PULL STATION
2=MON-USER-DEF-1
3=WATERFLOW
Event Code Screen
Pressing the down arrow key allows viewing of all Events associated with the
selected Communication Format. Pressing the number corresponding to the event
displayed in each screen will display its default event code which can be customized
by the programmer. For example, pressing 1 for Pull Station will display the
following screen which allows the Event Code to be changed from the default
value.
PULL STATION
ALARM
Event Code Screen
The tables on the following pages list all of the Events and their default Event
Codes for the various Communication Formats.
Communication Format Description
4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
Contact ID, DTMF, 1400/2300 ACK
000
Programming
107