Programming
SERVICE TERMINAL
1=PANEL ID
2=TERMINAL 1
3=TERMINAL 2
Service Terminal Screen #1
100
3.6.9.2.4.2 Terminal 1 and Terminal 2
Service Terminal #1 is generally designated as the FACP primary phone line used
for receiving phone calls from the service terminal (PC) being used for remote
programming. Service Terminal 2 is referred to as the secondary phone line.
Pressing 2 for Terminal 1 or 3 for Terminal 2 while viewing Service Terminal
Screen #1 will display the following screen:
SERVICE TERMINAL #
1=PHONE NUMBER
Service Terminal # Screen
Phone Number (Service Terminal)
The Service Terminal Phone Number will be used by the control panel to contact
the service terminal. Pressing 1 while viewing the Service Terminal # Screen will
cause the following screen to be displayed:
PHONE NUMBER
20 NUMBERS MAXIMUM
A flashing cursor will appear in the lower left corner. Enter the phone number for
the service terminal by keying in the first digit, pressing the left arrow key and
entering the second digit. Continue this process until all desired numbers have been
entered (maximum of 20 characters). Press the Enter key to store the phone number
in memory and return the display to the Service Terminal # Screen.
Valid entries are 0 - 9 and A - F with the numeric digits as dialed numbers and
letters representing the following functions:
A = * on a Touchtone phone keypad
B = # on a Touchtone phone keypad
C = look for secondary dial tone for up to two seconds (then dial anyway)
D = three second pause
E = five second pause
F = end of phone number (F is automatically entered for unused entry
positions)
Printer-PC Screen
MS-9200UDLS PN 52750:A 11/04/05