4: Walktest; 5: System - Honeywell Fire-Lite Alarms MS-9200UDLSE Manual

Fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms MS-9200UDLSE:
Table of Contents

Advertisement

Programming
PROGRAMMING
1=WALKTEST
2=SYSTEM
3=ZONE SETUP
Maintenance Screen #2
124
Pressing 3 while viewing Program Check screen will cause a screen similar to the
following to be displayed:
ZONES NO OUTPUT
05 07 09 10 11 1D001
The Zone No Output feature allows the programmer to view the zones which have not
been programmed to at least one output device (not including general alarm Zone 00).
The example in the preceding screen indicates that Zones 05, 07, 09, 10 and 11 have
been programmed to an addressable detector with an address of 001 on loop 1 but have
not been programmed to any output devices. Use the up and down arrow keys to view
all the zones without output assignments.
3.7.4 Walktest
To perform a walktest, press 1 while viewing Maintenance Screen #2. The following
screen will be displayed:
1=SILENT
2=AUDIBLE
3=VIEW RESULT
The operator can press 1 to perform a silent walktest or 2 to perform an audible
walktest. The display will read UNIT IN WALKTEST. To end the Walktest, press the
Esc (Escape) key.
Pressing 3 after the walktest has been completed, will allow the operator to view the
results of the walktest.
3.7.5 System
To program the time and date into the control panel, press 2 while viewing Maintenance
Screen #2. The following display will appear:
1=TIME/DATE
Maintenance Programming Level
WALKTEST
Walktest Screen
SYSTEMS
System Screen
MS-9200UDLS PN 52750:A 11/04/05