15: Print - Honeywell Fire-Lite Alarms MS-9200UDLSE Manual

Fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms MS-9200UDLSE:
Table of Contents

Advertisement

Operating Instructions
READ STATUS
1=SERVICE TERMINAL
2=PRINTER/PC
3=PRINT
Read Status Screen #5
DEVICE#
DEVICE TYPE
1D001
SMOKE (PHOTO)
1D002
SMOKE (PHOTO)
1D003
SMOKE (PHOTO)
1D004
SMOKE (PHOTO)
1D005
SMOKE (PHOTO)
1D006
SMOKE (PHOTO)
1D007
SMOKE (PHOTO)
1D008
SMOKE (PHOTO)
1D009
SMOKE (PHOTO)
150
4.22.15 Print
To print program data or control panel status, press 3 while viewing Read Status Screen
#5. The following screens will be displayed:
1=HISTORY
2=WALKTEST LOG
3=DETECTOR DATA
1=EXIT PRINTING
Pressing 1 while viewing Print Screen #1 allows the user to print the History file which
will detail all of the system activities since the file was last cleared from memory.
Pressing 2 while viewing Print Screen #1 allows the user to print the Walktest log
which will detail all of the system activations during walktest since the log was last
cleared. Refer to "Walktest" on page 95 for additional information on the display.
Pressing 3 while viewing Print Screen #1 allows the user to print the detector data for
each addressable smoke detector connected to the system. A printout, similar to the
following example, will be generated if an optional printer is connected to the FACP.
%DRIFT COMP
20
20
21
20
21
20
20
20
20
Chamber Value
The Chamber value should be within the indicated range for the following smoke
detectors:
SD350(T), D350P(R) and SD300(T) Addressable Photoelectric Smoke
Detectors: 405 - 2100 (obscuration of 1.00%/ft to 3.66%/ft.)
CP350 and CP300 Addressable Ionization Smoke Detectors: 750 - 2100
(obscuration of 0.50%/ft. to 1.44%/ft.)
If the addressable smoke detector's Chamber reading is not within the acceptable range,
clean the detector and check the Chamber value again. If the reading is still not within
the acceptable range, immediately replace the detector.
PRINT
Print Screen #1
PRINT
Print Screen #2
CHAMBER
TIME/DATE
1281
12:01AM 01-08-2001
1281
12:01AM 01-08-2001
1259
12:01AM 01-08-2001
1309
12:02AM 01-08-2001
1281
12:02AM 01-08-2001
1322
12:02AM 01-08-2001
1280
12:02AM 01-08-2001
1215
12:02AM 01-08-2001
1310
12:02AM 01-08-2001
MS-9200UDLS PN 52750:A 11/04/05
Read Status

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fire-lite alarms ms-9200udls