Honeywell Fire-Lite Alarms MS-9200UDLSE Manual page 63

Fire alarm control panel
Hide thumbs Also See for Fire-Lite Alarms MS-9200UDLSE:
Table of Contents

Advertisement

Master Programming Level
Monitor Type
Pull-Station
User-Defined-1
Waterflow
User-Defined-2
Monitor
User-Defined-3
Future
Future
Smoke-Conventional
User-Defined-5
Heat-Conventional
User-Defined-6
Medic-Alert
User-Defined-7
Hazard-Alert
User-Defined-8
Tornado-Alert
User-Defined-9
Future
Future
Tamper
User-Defined 11
Supervisory
User-Defined 12
Supervisory-AR
User-Defined 13
Power-Monitor
User-Defined 14
Trouble-Monitor
User-Defined-15
Process-Monitor
User-Defined 16
Process-Monitor-AR
User-Defined-17
Future
Future
Ack-Switch
Sil-Switch
Reset-Switch
Drill-Switch
PAS-Bypass
HVAC RESTART
HVAC OVRRIDE
Drill-Switch-AR
MS-9200UDLS PN 52750:A 11/04/05
Monitor module type selection will affect the function of the point as follows:
Table 3.1 Monitor Types
Action When Activated
Fire Alarm
same as previous (Pull-Station)
Fire Alarm Delayed
same as previous (Waterflow)
Fire Alarm
same as previous (Monitor)
not used
not used
Fire Alarm
same as previous (Smoke-Conventional)
Fire Alarm
same as previous (Heat-Detector)
Supervisory, latching
same as previous (Medic-Alert)
Supervisory, latching
same as previous (Hazard-Alert)
Supervisory, latching
same as previous (Tornado-Alert)
not used
not used
Supervisory, nonlatching (tracking)
same as previous (Tamper)
Supervisory, latching
same as previous (Supervisory)
Supervisory, nonlatching (tracking)
same as previous (Supervisory-AR)
Power Fault
same as previous (Power Monitor)
Trouble
same as previous (Trouble Monitor)
Piezo
same as previous (Process-Monitor)
Piezo, nonlatching (tracking)
same as previous (Process-Monitor-AR)
not used
not used
Acts like panel Acknowledge Key
Acts like panel Silence Key
Acts like panel Reset Key
Acts like panel Drill Key
PAS Disable
Switch
Switch
Acts like panel Drill Key, nonlatching (tracking)
Note:
1. For the PROCESS-MONITOR-AR selection, AR refers to AutoResettable
2. For HVAC RESTART and HVAC OVRRIDE descriptions, refer to "Monitor
Module Operation" on page 179
Programming
63