C.8.3 Vigilon Series Panels
For a fixed CLSS Gateway mainboard, we recommend using a UART/TTL connection. If it
is not available, use a RS-232 connection.

To Use a UART/TTL Connection

1. On the CLSS Gateway mainboard Side
Connect the male UART/TTL cable to the Rx (Red), Gnd (Silver), and Tx (White) UART/TTL
terminals of the CLSS Gateway mainboard.
The UART/TTL port is labeled as 5 in
2. On the Panel Side
1. Within the panel, find the backplane PCB board (see
2. Connect the 3.5mm phono socket to the P11 connector on the panel's PCB.
3. Power Connection
On the CLSS Gateway mainboard Side
Connect the power cable to a 24V DC external power source.
NOTE: The external power supply must be dedicated and not shared with any other
devices.
NOTE: The panel's power supply to the CLSS Gateway mainboard must be within +24V DC
power.

To Use an RS-232 Port via an I/O Card

Using an add-on I/O card (VIG-IOC-DOM), certain Vigilon panel variants can
communicate with the CGW-MB.
The I/O card has a rotary switch, which should point to 5.
The baud rate of the I/O card should be 19200.
CGW-MB Installation and Users' Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022