Honeywell CGW-MB Installation And User Manual page 140

Som module
Table of Contents

Advertisement

AM Series Panels
Figure C.3: Wiring Diagram: RS-232 Connection with AM8200 Panel
Power Connection
Using a power cable, the CLSS Gateway mainboard can connect to the 24V DC power
supply module of the AM8200 panel.
NOTE:
- Use the details given on the power supply module of the panel.
- The panel's power supply to the CLSS Gateway mainboard must be within +24V DC
power.
On the CLSS Gateway mainboard Side
• Ensure that the RS-232 cable is connected in the RS-232 port of the CLSS Gateway
mainboard.
On the Panel Side
• Connect the Red wire to the +ve pin of the AM82-MB board.
• Connect the Black wire to the -ve pin of the AM82-MB board.
CGW-MB Installation and Users' Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
Connecting to the Panels
139

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents