Read Device Identification (0x2B/0x0E)

7.22.3 CLSS Gateway mainboard Information Input Registers
NOTE: Information/debug values are used by the CGW-MB Unit ID only. All other nodes
reject reads in this address range.
The CGW-MB records some status and configuration information for debugging and
technical support purposes. This information is stored in some Reserved CLSS Gateway
mainboard registers as outlined below.
CLSS Gateway mainboard Modbus Address
CLSS Gateway mainboard IP Address
CLSS Gateway mainboard Version Number
Table 7.33: CLSS Gateway mainboard Information Input Register Addresses
Start Address
360001
320001
360016
360017
360018
360019
7.22.4 Node Status Details
Each nodes status is represented by a bit in a register. If the bit is set, the node is on line.
Below table provides an example of how this is represented in a register.
Address
15
320001
N16
320002
N32
7.23 Read Device Identification (0x2B/0x0E)
This function code allows reading the identification and additional information about the
CGW-MB.
CGW-MB Installation and Users' Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
End Address
360100
320015
360016
360017
360018
360019
Table 7.34: Node Status Example
14
13
12
11
N15 N14 N13 N12 N11 N10
N31 N30 N29 N28 N27 N26 N25 N24 N23 N22 N21 N20 N19
Table 7.35: Read Device Identification (Ox2B/OxOE)
Object Name /
Object
Description
ID
0x00
VendorName
0x01
ProductCode
0x02
MajorMinorRevision
0x03
VendorUrl
0x04
ProductName
0x05
ModelName
Information/Debug information
Node Status:
1 = On Line
0 = Off Line
The CGW-MB tracks status of network nodes
under Modbus feature monitoring.
CLSS Gateway mainboard major version
number
CLSS Gateway mainboard minor version
number
CLSS Gateway mainboard feature number
CLSS Gateway mainboard build number
Bit Number
10
9
8
7
N9
N8
N7
Notifier
1
V1.0 (Example)
www.notifier.com
Modbus CLSS
Gateway mainboard
Modbus CLSS
Gateway mainboard
Modbus Communications
Description
6
5
4
3
N6
N5
N4
N3
Value
2
1
0
N2
N1
N18
N17
67