Honeywell CGW-MB Installation And User Manual page 128

Som module
Table of Contents

Advertisement

BACnet PIC Statement
Supported - Binary Value Object
Present Value
Event State
Reliability
Status Flags
Out of Service
CGW-MB Installation and Users' Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
BACnet
Enumeration
0
bpv_InActive
1
Bpv_Active
BACnet
BACnet Event
Enumeration
0
EsNormal
1
EsFault
2
EsOffNormal
BACnet
Enumeration
0
reNoFaultDet
ected
7
re_Unreliable
Other
BACnet Status
Boolean
0,0,0,0
Normal
1,0,0,0
InAlarm
0,1,0,0
Fault
0,0,0,1
OutOfService
1,0,0,1
InAlarm,
OutOfService
0,1,0,1
Fault,
OutOfService
Boolean
0
FALSE
1
TRUE
Trouble, Device Disabled, Normal
Activation
State
Normal
Trouble, Device Disabled
Activation
BACnet
Reliability
Activation, Device Disabled, Normal
Trouble
Flags
Normal
Activation
Trouble
Device Disabled
If device is in Alarm state (
Activation) and also device goes to
disable state(Device Disabled)
If device is in trouble state
(Trouble)and also device goes to
disable state(Device Disabled)
All statuses other than disable
Device Disabled
The BACnet Feature
Fire Panel State
Fire Panel State
Fire Panel State
Fire Panel State
Fire Panel State
127