BACnet PIC Statement
IO channels (Multi State Input or Multi State Output)
((Loop - 1) x 3000) + 18000 + ((#Point_Address - 1) * 12) + #CHANNEL_ADDR (1 to 12)
Example:
L01D200 Channel 1, ->
L01D200 Channel 2, ->
L01D200 Channel 12, ->
Panel Circuits (BINARY_OUTPUT)
(Panel# x 10) + (circuit# - 1) + 650
Bell Circuits or NAC Circuits (BINARY_OUTPUT)
(BELL_CIRCUIT# + 790)
Zones (MULTI_STATE_INPUT or LIFE_SAFETY_ZONE)
ZONE (1-2000) => (ZONE# + 10000)
Logic Zones (MULTI_STATE_INPUT or LIFE_SAFETY_ZONE)
LZONE (1-2000) => (LZONE# + 12000)
Special Zones (MULTI_STATE_INPUT or LIFE_SAFETY_ZONE)
FZONE (0-47) => (FZONE# + 14000)
Trouble Zones (MULTI_STATE_INPUT or LIFE_SAFETY_ZONE)
TZONE (1-99) => (TZONE# +14100)
Releasing Zones (MULTI_STATE_INPUT or LIFE_SAFETY_ZONE)
RZONE (0-9) => (RZONE# + 14050)
Command Build( BINARY_VALUE)
#COMMAND_BUILD_NUM + 15000
DAA Speaker Circuit
(DAA# - 1) x 4 + (Spk# - 1) + 2600
AFP 2800 Specific
// AZF 1 and 2
(AZF# + 3600)
// R00M003I 1-4
(R00M003I# + 3602)
// Relays 1 through 8
(Relay# + 3606)
// XR Relays 1-64
(XR Relay# + 3620)
System Troubles or Generic Panel Points
(System Trouble# + 14200)
800 addresses are dedicated to system troubles or generic panel points. Bucketized the
troubles as mentioned below.
CGW-MB Installation and Users' Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
((1-1) x 3000) + 18000 + ((200 - 1) * 12) + 1 = MSO20389
((1-1) x 3000) + 18000 + ((200 - 1) * 12) + 2 = MSO20390
((1-1) x 3000) + 18000 + ((200 - 1) * 12) + 12 = MSI20400
The BACnet Feature