To Connect with the BACnet Client
8.10.1 To Configure the BACnet Settings
CGW-MB control is enabled through a web page-based configuration tool running on the
CLSS Gateway mainboard. Enable the control as follows:
1. On the CGW-MB board, find the S6 button.
2. Press the S6 button for a minimum of 6 seconds and then release it. It will switch the
CLSS Gateway mainboard to configuration mode.
The LED indicator DL3 turns ON and SOLID indicating that the configuration is
enabled.
3. Connect the Ethernet cable to Eth0 for enabling web configuration.
NOTE: The web configuration is available only on Eth0.
4. Open the Configuration Computer connected to the Eth0 port of the CLSS Gateway
mainboard.
NOTE: The static IP of the Eth0 port is 192.168.10.190.
5. In the Chrome browser, enter the following URL:
https://192.168.10.190:9443/config/index.html
6. Do the following if any security warning is shown. Otherwise, go to step 7.
1. Click the Advanced link below the error message.
2. Agree to proceed.
7. In the CLSS Gateway mainboard Configuration Tool page, enter the password.
NOTE: The default password is: Welcome123
8. Go to the Network Settings in the CLSS Gateway mainboard Settings section.
9. Assign the Eth1 port with a static IP address for the BACnet connection.
10.Connect the Ethernet cable between the Eth1 port of CGW-MB and its LAN device.
CGW-MB Installation and Users' Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
The BACnet Feature
117