Gent Panels
C.8 Gent Panels
C.8.1 Connection Options
The CLSS Gateway mainboard operates only with the Gent fire alarm control panels as
listed in the table below:
NOTE: The add-on I/O card (VIG-IOC-DOM) is ordered separately.
C.8.2 Compact Series Panels
For a fixed CLSS Gateway mainboard we recommend using the RS-232 connection. For a
portable CLSS Gateway mainboard, we recommend using the USB connection.

To Use a RS-232 Connection

Certain Gent panel variants can directly communicate through the RS-232 connection.
1. On the CLSS Gateway mainboard Side
Connect the RS-232 cable with pre-formed connector to the RS-232 port of the CLSS
Gateway mainboard board.
The RS-232 port is labeled as 6 in the
2. On the Panel Side
• The baud rate should be 19200.
At the PB6 terminal of the panel,
• Connect the White wire to a Rx1 or Rx2 pin.
• Connect the Brown wire to a Tx1 or Tx2 pin.
• Connect the Green wire to the 0V pin.
NOTE: Connect either the Tx1 and Rx1 or the Tx2 and Rx2.
NOTE: If Tx1 and Rx1 are connected, select the Port 1 settings in the panel for
communication. If Tx2 and Rx2 are connected, select the Port 2 settings in the panel for
communication.
CGW-MB Installation and Users' Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
Table C.6: Gent Panel Connection Options
Fire Alarm Panel Models
COMPACT-24-N
COMPACT-PLUS
VIGPLUS-24
VIGPLUS-72
VIG1-24
VIG1-72
1
Use the add-on I/O card (VIG-IOC-DOM) on the panel.
RS-485
UART/TTL
No
No
No
No
No
Yes
No
Yes
No
Yes
No
Yes
Figure
C.2.
Connecting to the Panels
RS-232
USB
Yes
Yes
Yes
Yes
1
Yes
Yes
1
Yes
Yes
1
Yes
Yes
1
Yes
Yes