C.5: Farenhyt Panels; C.5.1: Connection Options; C.5.2: To Use An Rs-485 Connection - Honeywell CGW-MB Installation And User Manual

Som module
Table of Contents

Advertisement

Farenhyt Panels
C.5 Farenhyt Panels
C.5.1 Connection Options
The CLSS Gateway mainboard operates only with the Farenhyt fire alarm control panels
as listed in the table below:
CAUTION: WHEN SUPPORTING THE ALARM TRANSMISSION, IT IS RECOMMENDED THAT THE
!
FARENHYT PANEL SHOULD USE SECONDARY ANN BUS CHANNEL WITH CLASS A WIRING.
IF THE ALARM TRANSMISSION SERVICE IS NOT USED, THE PANEL CAN USE EITHER THE PRIMARY OR
THE SECONDARY ANN BUS CHANNEL FOR THE CGW-MB CONNECTION.
Minimum Required Versions
For the CGW-MB: 3.2.4.12
C.5.2 To Use an RS-485 Connection
Using an RS-485 cable the CGW-MB connects with the annunciator primary terminal of
the panel.
CAUTION: CONNECT EITHER THE CGW-MB OR THE ANN S/P G MODULE WITH THE PANEL. BOTH OF
!
THEM SHOULD NOT BE CONNECTED TOGETHER WITH THE PANEL.
1. On the CLSS Gateway mainboard Side
At the RS-485 A port in the CLSS Gateway mainboard board:
• Connect the A connector to the IN+ pin of the RS-485 A port.
• Connect the B connector to the IN- pin of the same RS-485 A port.
The RS-485 ports in the CLSS Gateway mainboard board are labeled as 3 and 4 in the
Figure
C.2.
2. On the Panel Side
At the S-BUS board in the ANN-BUS PRI terminal:
• Connect the RS-485 +ve wire to the A port.
• Connect the RS-485 -ve wire to the B port.
3. Power Connection
On the CLSS Gateway mainboard Side
In the power supply port (labeled 7 in the
• Connect the Red wire to the +24V pin.
• Connect the Black wire to the Gnd pin.
CGW-MB Installation and Users' Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
Table C.3: Farenhyt Panel Connection Options
Fire Alarm Panel Models
Panel firmware version: 6.05.03
IFP-75
IFP-300
IFP-300ECS
IFP-2100
IFP-2100ECS
Panel firmware version: 5.0
IFP-50
IFP-100
IFP-100ECS
IFP-1000
IFP-1000ECS
IFP-2000
IFP-2000ECS
RS-485
UART/TTL
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Figure
C.2):
Connecting to the Panels
RS-232
USB
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
151

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents