3: To Locally Upgrade With A Pc; 4: To Verify The Upgrade; 5: Led Indications During The Upgrade - Honeywell CGW-MB Installation And User Manual

Som module
Table of Contents

Advertisement

Upgrading the CLSS Gateway mainboard Firmware
6.1.3 To Locally Upgrade with a PC
1. On the CLSS Gateway mainboard side, connect an Ethernet cable to the Ethernet port
(J3). The port is labeled as 2 in
2. On the configuration computer side, connect the Ethernet cable to the configuration
computer's Ethernet port.
3. On the CLSS Gateway mainboard board, find the S6 button.
4. To switch to the configuration mode, press and hold the S6 button for a minimum of 6
seconds, and then release it. The LED indicator DL3 turns ON and SOLID, indicating
that the configuration is enabled.
5. Open the Chrome browser and enter the following IP address for the configuration
tool:
https://192.168.10.190:9443/config/index.html
6. In the Sign In page, enter the password.
NOTE:The default password is: Welcome123
7. In the list of settings options, click Diagnostic.
8. In the CLSS Gateway mainboard FIRMWARE UPGRADE section, click Choose File.
9. Select the firmware image file and click Choose.
10.Once the chosen file is uploaded, click Upgrade.
6.1.4 To Verify the Upgrade
1. After the restart, log into the configuration tool.
2. Click Diagnostic.
3. Click About and verify that the new version of the CLSS Gateway mainboard firmware
is shown.
6.1.5 LED Indications During the Upgrade
While the CLSS Gateway mainboard is downloading the firmware, the Green-color LED
indicator DL4 will be ON.
If an LED is indicating differently, refer
necessary, refer to the
Honeywell Technical Support.
CGW-MB Installation and Users' Manual | P/N:LS10248-000HW-E | REV.G | JUL/31/2022
Figure 6.1: Firmware Upgrade
Figure
4.1.
Table 2.2
6.2, "Troubleshooting"
to determine the operational status. If
section to fix the problem or contact
Post-Installation Activities