Download Print this page

AEG ME10 Manual page 68

Power circuit breaker

Advertisement

BREAKER ME10
If the Circuit Breaker has tripped on a
overcurrent event the thermal effects of the
current previously running in the circuit will be
taken into account. (remembered). This can
result in a prevention of breaker re-closure onto
a circuit running in 'Hot conditions' or cause the
mentioned reduction in the total tripping time
after re-closure.
The trip unit tracks these occurrences across a
time frame of 12 minutes.
2.2.10 Neutral Protection
Four pole ME10 circuit breakers are equipped
with a neutral pole located on the left, when
viewed from the breaker front.
The ME10 trip unit allows the neutral pole to be
optioned with or without a full set of protection
devices. When neutral protection is chosen the
LT (overload) protection device in the neutral
pole can be set at on of three different values.
Choosing neutral protection and the value
thereof depends on the network and installation
configuration.
The following options are available:
-- Neutral unprotected (0%)
– Neutral protected and the LT protection set at
one of three values:
-- 50% Half Neutral protection
-- 63% Neutral Protection
-- 100% Full Neutral protection)
Setting the LT device in the Neutral pole
influences other installed protection devices (if
present) as indicated in table 2.16:
Table 2.16
Neutral
Protection
setting
Device
LT
SD
100 %
I
RELT
Gf sum
LT
SD
63 %
I
RELT
Gf sum
LT
SD
I
50 %
RELT
Gf sum
LT
SD
I
0 %
RELT
Gf sum
2-24
INTRO
BREAKER
TRIP UNIT
Überstromvorfall ausgelöst hat, wird der
thermische Effekt der aktuellen, zuvor
abgelaufenen Schaltungen berücksichtigt.
(Erinnerungseffekt). Dies führt zur Vermeidung
von Wiedereinschaltungen auf eine Schaltung,
die unter 'heißen Bedingungen' läuft oder führt
dazu, dass die erwähnte Kürzung der Gesamt-
Auslösezeit nach Wiedereinschaltung eintritt.
Die Auslöseeinheit speichert dies Vorgänge
innerhalb eines Zeitfensters von 12 Minuten.
2.2.10 Neutralschutz
Vierpolige ME10 Leistungsschalter sind mit einer
neutralen Polbahn auf der linken Seite (von vorn
gesehen) ausgestattet.
Die ME10 Auslöseeinheit ermöglicht die
Bestimmung des neutralen Pols mit oder ohne
einen vollständigen Geräteschutz. Wenn ein
Neutralleiterschutz gewählt wird, kann der LT
(Überlast) Geräteschutz des neutralen Pols auf
drei verschiedene Werte eingestellt werden. Die
Wahl Neutralleiter-Schutz und deren Wert hängt
von der Netzwerk-Konfiguration ab.
Die folgenden Optionen stehen zur Verfügung:
-- Neutralleiter ungeschützten (0%)
-- Neutralleiter geschützt mit dem LT-Schutz
auf einen der drei Werte:
-- 50% halber Neutralleiterschutz
-- 63% Neutralleiterschutz
-- 100% voller Neutralleiterschutz
Einstellen der LT-Geräte auf Neutralleiterschutz
beeinflussen andere installierte Schutzarten
(falls vorhanden) siehe Tab. 2.16:
Tab. 2.16
Device setting
Neutralleiter
in Neutral pole
Einstellung
100%
100%
100%
100 %
100%
100%
63%
63%
63%
63 %
63%
63%
50%
50%
50%
50 %
50%
50%
0%
0%
0%
0 %
0%
0%
LOCKS
ACCESSORIES
Geräteeinstellung
Schutzart
im Neutral-Pol
LT
100%
SD
100%
I
100%
RELT
100%
Gf sum
100%
LT
63%
SD
63%
I
63%
RELT
63%
Gf sum
63%
LT
50%
SD
50%
I
50%
RELT
50%
Gf sum
50%
LT
0%
SD
0%
I
0%
RELT
0%
Gf sum
0%
TESTS
APPENDIX
Se l'interruttore è intervenuto su un evento di
sovracorrente, saranno presi in considerazione
gli effetti termici della corrente
precedentemente circolante nel circuito (ovvero
saranno ricordati tali valori). Ciò può evitare la
richiusura dell'interruttore su un circuito
operante in "condizioni calde" o ridurre il tempo
totale di intervento dopo la richiusura.
Il Relè di Protezione traccia questi eventi in un
periodo di tempo di 12 minuti.
2.2.10 Protezione Neutro
Gli interruttori quadripolari ME10 sono dotati di
un polo neutro situato a sinistra guardando
l'interruttore dalla parte anteriore.
Il Relè di Protezione ME10 permette di
equipaggiare opzionalmente il polo neutro con
una serie completa di dispositivi di protezione.
Quando viene scelta la protezione del neutro, il
dispositivo di protezione LT (sovraccarico) sul
polo neutro può essere impostato su tre valori
diversi. Scegliere o meno la protezione del
neutro e il relativo valore dipende dalla rete e
dalla configurazione di installazione.
Le opzioni disponibili sono le seguenti:
-- Neutro non protetto (0%)
-- Neutro protetto con protezione LT impostata
su uno dei tre valori:
-- protezione del neutro al 50%
-- protezione del neutro al 63%
-- protezione totale del neutro al 100%
L'impostazione del dispositivo LT sul polo neutro
influenza altri dispositivi di protezione installati
(se presenti), come indicato nella tabella 2.16:
Tabella 2.16
Impostazione
Dispositivo
del neutro
Protezione
LT
SD
100 %
I
RELT
Gf sum
LT
SD
63 %
I
RELT
Gf sum
LT
SD
I
50 %
RELT
Gf sum
LT
SD
I
0 %
RELT
Gf sum
Impostazione
dispositivo
sul polo neutro
100%
100%
100%
100%
100%
63%
63%
63%
63%
63%
50%
50%
50%
50%
50%
0%
0%
0%
0%
0%

Advertisement