Power circuit breaker

Advertisement

Configuring the Electronic trip unit (ETU) for
Voltage Conditioner:
Configure the trip unit (ETU) with following PT
ranges for Voltage conditioner catalogues listed..
GMPU1
PT voltage to be set to 230V
set PT connection as Phase to Neutral
GMPU2
PT voltage to be set to 400V
set PT connection as Phase to Neutral
GMPU3
PT voltage to be set to 250/290/415V
..as per the jumper wire settings of J5
connector described below.
set PT connection as Phase to Neutral
and...
GMPU4
PT voltage to be set to 690V
set PT connection as Phase to Phase
PT VOLTAGE
120
120
...save chosen value
J5 Connections GMPU3:
GMPU3 / 415V
Common
wire
250V
290V
415V
GMPU3 / 290V
Common
wire
250V
290V
415V
GMPU3 / 250V
Common
wire
250V
290V
415V
Fuse replacement
Sicherungswechsel
Sostituzione del fusibile
1. Use screw driver to open the botton plate
2. Take out the bottom plate which carries the PCB
3. Now the fuse is accessible.
Replace the fuse if needed...
Konfigurieren der Elektronik Auslöseeinheit (ETU)
für die Spannungswandler:
Anpassen der Auslöseeinheit (ETU) auf folgende
Trafo-Werte für die Spannungswandler den
Katalogdaten entsprechend..
GMPU1
Trafo-Spannung auf 230V zu setzen
GMPU2
Trafo-Spannung auf 400V zu setzen
GMPU3
Trafo-Spannung auf 250/290/415V
..mit der Leiterverbindung am J5 Anschlussblock die
Spannung wie unten beschrieben bestimmen
Anschlussart Phase-Nullleiter (Neutral)
und...
GMPU4
Trafo-Spannung auf 690V setzen
Anschlussart Phase-Phase
TRAFO
Spannung
690
120
J5 Verbindungen GMPU3:
GMPU3 / 415V
Common
250V
290V
415V
GMPU3 / 290V
Common
250V
290V
415V
GMPU3 / 250V
Common
250V
290V
415V
1. Bodenplatte mit dem Schraubenzieher öffnen
2. Bodenplatte mit Leiterplatte herausnehmen.
3. Die Sicherung ist jetzt zugänglich.
Bei Bedarf austauschen...
1
ACCESSORIES
Configurazione del Relè di Protezione elettronica
Configurare il Relè di Protezione (ETU) con i range di
GMPU1
GMPU2
GMPU3
GMPU4
120
690
...gewählten Wert sichern
Connessioni J5 GMPU3:
GMPU3 / 415V
Comune
Leitung
250V
290V
415V
GMPU3 / 290V
Comune
Leitung
250V
290V
415V
GMPU3 / 250V
Comune
Leitung
250V
290V
415V
1. Usare un cacciavite per aprire la piastra di fondo
2. Estrarre la piastra che supporta il PCB
3. Ora il fusibile è accessibile
Sostituire il fusibile se necessario...
2
BREAKER ME10
(ETU) per il regolatore di tensione:
tensione che corrispondono ai regolatori di
tensione seguenti..
Tensione PT da predisporre a 230V
predisporre i collegamenti PT come fase-neutro
Tensione PT da predisporre a 400V
predisporre i collegamenti PT come fase-neutro
Tensione PT da predisporre a
250/290/415V ..con un cavallotto, impostare il
cablaggio su J5 come descritto di seguito.
predisporre i collegamenti PT come fase-
neutroe...
Tensione PT da predisporre a 690V
predisporre i collegamenti PT come fase-fase
PT VOLTAGE
120
690
120
... salva il valore scelto
cavo
cavo
cavo
3
4
.4
4.4-21