Honeywell DL230 Operating Instructions Manual page 48

Table of Contents

Advertisement

48
Serv.  Edit and delete  ClCDL
Press the ENTER key  "0" flashes.
Change the value using the arrow buttons  or  to "1".
After you have entered the value, press the ENTER button to confirm
the input. The display shows as "busy" temporarily.
The certification data log is then deleted. The input value can be deleted
by using the ESC key.
5.3.1.9 Closing and securing the calibration lock
After all settings subject to calibration regulations have been adjusted,
close the calibration lock in the same way that it was opened: Press the
buttons described in chapter 5.3.1.1 once again.
The calibration switch is secured with an adhesive label as described in
chapter 5.3.2.2.
5.3.1.10
Use of the "HT/LT switch-over"
The DL230 also offers an option to carry out the switch over from the high
tariff meter (HT) to the low tariff (LT) meter.
Whether such a switch over has been parameterized can be found under:
Serv.  Input 1  Parameter settings  HTLT1
Serv.  Input 2  Parameter settings  HTLT2
or
Serv.  Input 3  Parameter settings  HTLT3
or
Serv.  Input 4  Parameter settings  HTLT4
or
If the displayed value is "-.-.-", then no switch over took place. If the value is
not equal to "-.-.-", then a switch over to the set event is taking place.
In principle two settings are possible:
a) Meter 1 counts, meter 2 does not
b) Meter 1 counts at high tariff (HT) and meter 2 at low tariff (LT)
In case b) the switch over between HT and LT should be parameterized via
a settings file. Switch over either takes place in a "time-dependent" manner
or "controlled by an input". With the inactive meter, the short description will
be shown flashing.
Adjustment is simple to carry out via enSuite configuration
software.
Parameterization of the device is described in the DL230
application manual.
,
Assembly, Connection and Putting into Operation