40
The wire cross-section for the connection to the integrated
power supply unit is 0.3 ... 2.5 mm
When using stranded wire, use appropriate wire ferrules.
Use only cables, which fit to the cable glands in order to keep
IP protection class also after the installation.
Minimum cable diameter:
Cable gland M12 ≥ 5 mm
Cable gland M16 ≥ 5,5 mm.
DANGER!
Danger to life from electrical current!
Connect the protective earthing of the mains power supply
to the J2 screw terminal, connection "E"!

5.2.4 Connect outputs of the DL230

DANGER!
The connection of non-intrinsically-safe or non-
associated apparatus presents a risk of explosion!
The operation of the DL230 as associated apparatus for zone
0 or 1 and the connection of non-intrinsically-safe equipment
which exceeds those conditions and limit values specified in
the declaration of conformity, presents a risk of explosion.
Therefore:
– When the DL230 is used as associated apparatus only
devices with intrinsically-safe circuits and electrical data
that corresponds to those requirements stipulated in the
ATEX declaration for the DL230 (see Appendix), should
be connected. Notice also the limitations of chapter 3.6.1.
– Screw the terminal covers over the connected output
terminals again.
The wire cross-section for the connection to the DL230 out-
puts is 0.3 ... 2.5 mm
When using stranded wire, use appropriate wire ferrules.
Assembly, Connection and Putting into Operation