Honeywell DL230 Operating Instructions Manual page 44

Table of Contents

Advertisement

44
5.3.1.2 Adjusting the parameters for the pulse transducer of the meter
If a pulse transducer is connected as per 0 then adjust the input mode and
the cp value as follows:
1. Setting the input mode:
Move the cursor to the "Serv." tab and via the path below to the input
mode "Md.E1":
Serv.  Input 1  Settings  Md.E1
Press the ENTER button  The set value flashes.
Repeatedly press one of the  or  arrow keys until the text "Pulse
Input" flashes.
Press the ENTER key to confirm the value setting. The input value can
be deleted by using the ESC key.
2. Setting the cp (pulse constant) value:
Move the cursor to cp value "cp.E1" in the same path
Press the ENTER  button. One of the value's digits flashes.
Move the cursor to the digits using the  or  arrow keys and update
them using the  or  arrow keys.
Press the ENTER key to confirm the value setting. The input value can
be deleted by using the ESC key.
The same process can also be used for the other inputs, inputs 2 to 4.
5.3.1.3 Activating encoder mode
If an encoder is connected as per 5.2.1.2, the encoder mode is activated as
follows:
Start the "Encoder Recognition" function using the DL230 keypad as
follows:
Move the cursor to the "Serv." register and to the value "Md.I1" (input
mode) via the following path:
Serv.  Input 1  Parameter settings  Md.I1
Press the ENTER button  the set value flashes.
Repeatedly press one of the  or  arrow keys until the value "Auto-
Encoder" flashes.
Press the ENTER key to confirm the value setting. Input can be can-
celled using the ESC key.
Wait until "Auto-Encoder" is replaced by another value. This can take
up to a minute as the DL230 activates and test all known encoder pro-
tocols consecutively.
Assembly, Connection and Putting into Operation

Advertisement

Table of Contents
loading

Table of Contents