B.4 MEMORY MAPPING
Table B–10: MODBUS MEMORY MAP (Sheet 58 of 58)
ADDR
REGISTER NAME
EC01
Synchrocheck 1 V1 Source
EC02
Synchrocheck 1 V2 Source
EC03
Synchrocheck 1 Maximum Voltage Difference
EC05
Synchrocheck 1 Maximum Angle Difference
EC06
Synchrocheck 1 Maximum Frequency Difference
EC07
Synchrocheck 1 Dead Source Select
EC08
Synchrocheck 1 Dead V1 Maximum Voltage
EC09
Synchrocheck 1 Dead V2 Maximum Voltage
EC0A
Synchrocheck 1 Live V1 Minimum Voltage
EC0B
Synchrocheck 1 Live V2 Minimum Voltage
B
EC0C
Synchrocheck 1 Target
EC0D
Synchrocheck 1 Events
EC0E
Synchrocheck 1 Block
EC10
Synchrocheck 1 Frequency Hysteresis
EC11
...Repeated for Synchrocheck 2
EC22
...Repeated for Synchrocheck 3
EC33
...Repeated for Synchrocheck 4
Settings File Template (Read/Write Setting)
ED00
FlexLogic Displays Active
ED01
Reserved
Setting File Template (Read Only Non-Volatile)
ED07
Last Settings Change Date
Settings File Template (Read/Write Setting)
ED09
Template Bitmask (750 items)
B-66
RANGE
0 to 5
0 to 5
0 to 400000
0 to 100
0 to 2
0 to 5
0 to 1.25
0 to 1.25
0 to 1.25
0 to 1.25
0 to 2
0 to 1
0 to 4294967295
0 to 0.1
0 to 1
---
0 to 4294967295
0 to 65535
D30 Line Distance Protection System
APPENDIX B
UNITS
STEP
FORMAT
---
1
F167
---
1
F167
V
1
F060
degrees
1
F001
Hz
0.01
F001
---
1
F176
1 (LV1 and DV2)
pu
0.01
F001
pu
0.01
F001
pu
0.01
F001
pu
0.01
F001
---
1
F109
---
1
F102
---
1
F300
Hz
0.01
F001
---
1
F102
---
---
F205
---
1
F050
---
1
F001
DEFAULT
0 (SRC 1)
1 (SRC 2)
10000
30
100
30
30
70
70
0 (Self-reset)
0 (Disabled)
0
6