GE D30D00HCHF8AH6AM6BP8BX7A Instruction Manual page 305

Ur series line distance protection system
Table of Contents

Advertisement

5 SETTINGS
The undervoltage delay setting defines the family of curves shown below.
where: T = operating time
D = undervoltage delay setting (D = 0.00 operates instantaneously)
V = secondary voltage applied to the relay
V
= pickup level
pickup
At 0% of pickup, the operating time equals the UNDERVOLTAGE DELAY setting.
NOTE
GE Multilin
D
T
--------------------------------- -
=
V
------------------
1
V
pickup
% of voltage pickup
Figure 5–91: INVERSE TIME UNDERVOLTAGE CURVES
D30 Line Distance Protection System
5.6 GROUPED ELEMENTS
842788A1.CDR
(EQ 5.19)
5
5-179