6 ACTUAL VALUES
PATH: ACTUAL VALUES
STATUS
DIRECT DEVICES
STATUS
MESSAGE
MESSAGE
These actual values represent the state of direct devices 1 through 16.
PATH: ACTUAL VALUES
STATUS
IEC 61850
GOOSE UINTEGERS
MESSAGE
MESSAGE
The D30 Line Distance Protection System is provided with optional IEC 61850 communications capability.
This feature is specified as a software option at the time of ordering. Refer to the Ordering section of chap-
ter 2 for additional details.
The IEC 61850 GGIO5 integer input data points are displayed in this menu. The GGIO5 integer data values are received
via IEC 61850 GOOSE messages sent from other devices.
PATH: ACTUAL VALUES
STATUS
TELEPROT CH TESTS
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The status information for two channels is shown here.
GE Multilin
DIRECT DEVICES STATUS
DIRECT DEVICE 1
STATUS: Offline
DIRECT DEVICE 2
STATUS: Offline
↓
DIRECT DEVICE 16
STATUS: Offline
IEC 61850 GOOSE UINTEGERS
UINT INPUT
1
0
UINT INPUT
2
0
↓
UINT INPUT 16
0
TELEPROT CH TESTS
CHANNEL 1
STATUS: n/a
CHANNEL 1 LOST
PACKETS:
1
CHANNEL 2
STATUS: n/a
CHANNEL 2 LOST
PACKETS:
1
VALIDITY OF CHANNEL
CONFIGURATION: FAIL
D30 Line Distance Protection System
6.2.16 DIRECT DEVICES STATUS
Range: Offline, Online
Range: Offline, Online
Range: Offline, Online
6.2.17 IEC 61850 GOOSE INTEGERS
6.2.18 TELEPROTECTION CHANNEL TESTS
Range: n/a, FAIL, OK
Range: 1 to 65535 in steps of 1
Range: n/a, FAIL, OK
Range: 1 to 65535 in steps of 1
Range: n/a, FAIL, OK
6.2 STATUS
6
6-9