5.2 PRODUCT SETUP
5
The D30 supports the Distributed Network Protocol (DNP) version 3.0. The D30 can be used as a DNP slave device con-
nected to multiple DNP masters (usually an RTU or a SCADA master station). Since the D30 maintains two sets of DNP
data change buffers and connection information, two DNP masters can actively communicate with the D30 at one time.
The IEC 60870-5-104 and DNP protocols cannot be used simultaneously. When the IEC 60870-5-104 FUNCTION
setting is set to "Enabled", the DNP protocol is not operational. When this setting is changed it does not become
NOTE
active until power to the relay has been cycled (off-to-on).
The DNP Channels sub-menu is shown below.
PATH: SETTINGS
PRODUCT SETUP
 DNP CHANNELS
The
DNP CHANNEL 1 PORT
for each channel. Once DNP is assigned to a serial port, the Modbus protocol is disabled on that port. When this setting is
set to "Network - TCP", the DNP protocol can be used over TCP/IP on channels 1 or 2. When this value is set to "Network -
UDP", the DNP protocol can be used over UDP/IP on channel 1 only. Refer to Appendix E for additional information on the
DNP protocol.
Changes to the DNP CHANNEL 1 PORT and DNP CHANNEL 2 PORT settings take effect only after power has
been cycled to the relay.
NOTE
Do not set more than one protocol to the same TCP/UDP port number, as this results in unreliable operation of
those protocols.
The
setting is the DNP slave address. This number identifies the D30 on a DNP communications link. Each
DNP ADDRESS
DNP slave should be assigned a unique address.
5-28
DNP MESSAGE FRAGMENT
MESSAGE
SIZE: 240
DNP OBJECT 1
MESSAGE
DEFAULT VARIATION: 2
DNP OBJECT 2
MESSAGE
DEFAULT VARIATION: 2
DNP OBJECT 20
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 21
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 22
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 23
MESSAGE
DEFAULT VARIATION: 2
DNP OBJECT 30
MESSAGE
DEFAULT VARIATION: 1
DNP OBJECT 32
MESSAGE
DEFAULT VARIATION: 1
DNP NUMBER OF PAIRED
MESSAGE
CONTROL POINTS: 0
DNP TCP CONNECTION
MESSAGE
TIMEOUT: 120 s

COMMUNICATIONS
DNP CHANNEL 1 PORT:
NETWORK
DNP CHANNEL 2 PORT:
MESSAGE
COM2 - RS485
and
DNP CHANNEL 2 PORT
D30 Line Distance Protection System
Range: 30 to 2048 in steps of 1
Range: 1, 2
Range: 1, 2, 3
Range: 1, 2, 5, 6
Range: 1, 2, 9, 10
Range: 1, 2, 5, 6
Range: 1, 2, 5, 6
Range: 1, 2, 3, 4, 5
Range: 1, 2, 3, 4, 5, 7
Range: 0 to 32 in steps of 1
Range: 10 to 7200 s in steps of 1

DNP PROTOCOL
DNP CHANNELS
Range: NONE, COM2 - RS485,
FRONT PANEL - RS232, NETWORK - TCP,
NETWORK - UDP
Range: NONE, COM2 - RS485,
FRONT PANEL - RS232, NETWORK - TCP,
NETWORK - UDP
settings select the communications port assigned to the DNP protocol