5 SETTINGS
The report control configuration settings are shown below:
PATH: SETTINGS
PRODUCT SETUP
CONFIGURABLE REPORT 1
 REPORT 1
 DATASET ITEMS
MESSAGE
MESSAGE
MESSAGE
To create the dataset for logical node LN, program the
attributes supported by the D30. Changes to the dataset will only take effect when the D30 is restarted. It is recommended
to use reporting service from logical node LLN0 if a user needs some (but not all) data from already existing GGIO1,
GGIO4, and MMXU4 points and their quantity is not greater than 64 minus the number items in this dataset.
The breaker configuration settings are shown below. Changes to these values will not take effect until the UR is restarted:
PATH: SETTINGS
PRODUCT SETUP
 XCBR
 CONFIGURATION
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
The
setting represents the breaker operating counter. As breakers operate by opening and closing, the
CLEAR XCBR1 OpCnt
XCBR operating counter status attribute (OpCnt) increments with every operation. Frequent breaker operation may result
in very large OpCnt values over time. This setting allows the OpCnt to be reset to "0" for XCBR1.
GE Multilin


COMMUNICATIONS
REPORT 1 DATASET ITEMS
ITEM
1:
ITEM
2:
ITEM
3:
ITEM 64:
ITEM 1


COMMUNICATIONS
XCBR1 ST.LOC OPERAND
Off
XCBR2 ST.LOC OPERAND
Off
XCBR3 ST.LOC OPERAND
Off
XCBR6 ST.LOC OPERAND
Off
CLEAR XCBR1 OpCnt:
No
CLEAR XCBR2 OpCnt:
No
CLEAR XCBR3 OpCnt:
No
CLEAR XCBR6 OpCnt:
No
D30 Line Distance Protection System

IEC 61850 PROTOCOL
REPORT CONTROL CONFIGURATION
Range: all valid MMS data item references
Range: as shown above
Range: as shown above
Range: as shown above
to
settings to a value from the list of IEC 61850 data
ITEM 64

IEC 61850 PROTOCOL
XCBR CONFIGURATION
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: No, Yes
Range: No, Yes
Range: No, Yes
Range: No, Yes
5.2 PRODUCT SETUP