GE D30D00HCHF8AH6AM6BP8BX7A Instruction Manual page 22

Ur series line distance protection system
Table of Contents

Advertisement

1.3 ENERVISTA UR SETUP SOFTWARE
3.
Select the Internet Protocol (TCP/IP) item from the list, and click the Properties button.
1
4.
Click the "Use the following IP address" box.
5.
Enter an IP address with the first three numbers the same as the IP address of the D30 relay and the last number dif-
ferent (in this example, 1.1.1.2).
6.
Enter a subnet mask equal to the one set in the D30 (in this example, 255.0.0.0).
7.
Click the OK button to save the values.
Before continuing, test the Ethernet connection.
1.
Open a Windows console window by selecting Start > Run from the Windows Start menu and typing "cmd".
2.
Type the following command, substituting the IP address of 1.1.1.1 with yours:
C:\WINNT>ping 1.1.1.1
3.
If the connection is successful, the system returns four replies similar to the following:
Pinging 1.1.1.1 with 32 bytes of data:
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Reply from 1.1.1.1: bytes=32 time<10ms TTL=255
Ping statistics for 1.1.1.1:
Packets: Sent = 4, Received = 4, Lost = 0 (0% loss),
Approximate round trip time in milliseconds:
Minimum = 0ms, Maximum = 0ms, Average = 0 ms
4.
Note that the values for
5.
If the following sequence of messages appears when entering the
1-12
and
vary depending on local network configuration.
time
TTL
D30 Line Distance Protection System
1 GETTING STARTED
command:
C:\WINNT>ping 1.1.1.1