GE D30D00HCHF8AH6AM6BP8BX7A Instruction Manual page 144

Ur series line distance protection system
Table of Contents

Advertisement

5.2 PRODUCT SETUP
Supervisor Role: When enabled (i.e., "Yes" is selected) the Supervisor role is active. When "No" is selected this role is dis-
abled. To disabled this setting a Supervisor authentication is necessary. If disabled, the Supervisor role is not allowed to log
on. In this case the Administrator can change the settings under the Supervisory menu.
If enabled, Supervisor authentication is required to change the settings in the Supervisory menu. If the Supervisor disables
his role after authentication, the Supervisor session remains valid until he switches to another role using MMI or until he
ends the current Supervisor session if using communications.
This role is disabled by default.
Factory Service Mode:
ting to become enabled a Supervisor authentication is necessary. The default value is Disable.
Serial Inactivity Timeout: The role logged via a serial port is auto logged off after the Serial Inactivity timer times out. A
separate timer is maintained for RS232 and RS485 connections. The default value is 1 minute.
SELF TESTS
PATH: SETTINGS
PRODUCT SETUP
 SELF TESTS
Failed Authentications: If this setting is Enabled then the number of failed authentications is compared with the Session
5
lockout threshold. When the Session lockout threshold is exceeded, this minor alarm indication comes up.
Firmware Lock: If this setting is Enabled then any firmware upgrade operation attempt when the "LOCK FIRMWARE
UPGRADE" setting is set to "Yes" brings up this self test alarm.
Settings Lock: If this setting is Enabled then an unauthorized write attempt to a setting for a given role activates this self
test.
PATH: SETTINGS
PRODUCT SETUP
 FAILED
 AUTHENTICATE
g) SYSLOG FORMAT
System logs are produced with the CyberSentry option. The format is as follows.
Security log
Event Number
Event Number — Event identification number (index)
Date & Timestamp — UTC date and time
Username — 255 chars maximum, but in the security log it is truncated to 20 characters
IP address — Device IP address
Role — 16 bit unsigned, of type format F617
ENUMERATION
ROLE
0
None
1
Administrator
2
Supervisor
3
Engineer
4
Operator
5
Factory
5-18
When enabled (i.e., "Yes" is selected) the device can go into factory service mode. For this set-

SECURITY
SUPERVISORY
 FAILED
 AUTHENTICATE
FIRMWARE LOCK:
MESSAGE
Enabled
SETTINGS LOCK:
MESSAGE
Enabled

SECURITY
SUPERVISORY
FAILED AUTHENTICATE:
Enabled
Date &
Timestamp
D30 Line Distance Protection System
SELF TESTS
See below
Range: Enabled, Disabled
Range: Enabled, Disabled
SELF TESTS
FAILED AUTHENTICATE
Range: Enabled, Disabled
Username
IP address
5 SETTINGS
Role
Activity Value
GE Multilin