GE D30D00HCHF8AH6AM6BP8BX7A Instruction Manual page 404

Ur series line distance protection system
Table of Contents

Advertisement

7.2 TARGETS
A
RELAY OUT OF SERVICE
b) MAJOR SELF-TEST ERROR MESSAGES
The major self-test errors are outlined in this section.
INCOMPATIBLE H/W:
Contact Factory (xxx)
Latched target message: Yes.
Description of problem: One or more installed hardware modules is not compatible with the D30 order code.
How often the test is performed: Module dependent.
What to do: Contact the factory and supply the failure code noted in the display. The "xxx" text identifies the failed mod-
ule (for example, F8L).
EQUIPMENT MISMATCH:
with 2nd line detail
Latched target message: No.
Description of problem: The configuration of modules does not match the order code stored in the D30.
How often the test is performed: On power up. Afterwards, the backplane is checked for missing cards every five sec-
onds.
What to do: Check all modules against the order code, ensure they are inserted properly, and cycle control power. If
the problem persists, contact the factory.
FLEXLOGIC ERROR:
with 2nd line detail
Latched target message: No.
Description of problem: A FlexLogic equation is incorrect.
How often the test is performed: The test is event driven, performed whenever FlexLogic equations are modified
What to do: Finish all equation editing and use self tests to debug any errors.
7
UNIT NOT PROGRAMMED:
Check Settings
Latched target message: No.
Description of problem: The
grammed.
How often the test is performed: On power up and whenever the
setting is altered
.
What to do: Program all settings and then set
c) MINOR SELF-TEST ERROR MESSAGES
Most of the minor self-test errors can be disabled. Refer to the settings in the User-programmable self-tests section in the
Settings chapter for additional details.
MODULE FAILURE___:
Contact Factory (xxx)
Latched target message: Yes.
7-6
event is recorded.

PRODUCT SETUP
INSTALLATION
PRODUCT SETUP
D30 Line Distance Protection System
7 COMMANDS AND TARGETS
setting indicates the D30 is not pro-
RELAY SETTINGS

PRODUCT SETUP
INSTALLATION

INSTALLATION
RELAY SETTINGS
.
RELAY SETTINGS
to "Programmed".
GE Multilin

Advertisement

Table of Contents
loading

This manual is also suitable for:

D30

Table of Contents