5.7.4 Multi-function analog output : H3.01~H3.03

5.7.4.1 Setting multi-function analog output : H3.01
Parameter
Name
Unit
No.
Analog Monitor
H3.01
Function Setting
• H3.01 is used to select the function of the analog monitor output
terminal.
• Setting
Setting
Function
constant
0
Frequency command
1
Output frequency
2
Output current
3
Output voltage
4
DC voltage
5
Output power
6
Motor speed
7
Estimated torque
5. Parameters
5-55
Changeable
Setting
Factory
during
range
Setting
operation
-
0~7
1
X
Reference
U0.01
U0.02
U0.03
U0.04
U0.05
U0.06
U0.07
U0.08
MOSCON-E7 User's Manual
5-56
5.7.4.2 Adjusting the monitor output : H3.02, H3.03
Parameter
Name
Unit
No.
Analog Monitor
H3.02
0.1%
Gain setting
Analog Monitor
H3.03
0.1%
Bias setting
• H3.02 and H3.03 are used to set the gain and bias of monitor output.
• H3.02 : set what multiple of 10V will correspond to a 100% output of
the monitored item.
• H3.03: set the amount that the output characteristic will be shifted
vertically. Set this amount as a percentage, with 10V corresponding to
100%.
Gain
Max. Output Frequency x
100
Bias
Max. Output Frequency x
100
Use the current value in parenthesis
when current input has been selected

Figure 5.23 Monitor output adjustments

Changeable
Setting
Factory
during
range
Setting
operation
0.0
100.0
O
~200.0
-100.0
0.0
O
~100.0
When H3.01=0
Frequency
Command
Analog output
0V