• Active source of RUN command in local and remote mode can be
selected independently as follows.
Digit1
B0.02
Active source of RUN
command in local mode (0~1)
• Setting
Setting
Reference source
constant
0
Operator (RUN/STOP key on keypad)
1
Contact input (contact 1 or 2 on terminal block)
2
Communication (RS-485)

5.3.1.3 Selecting stopping method : B0.03

Parameter
Name
Unit
No.
Stopping
B0.03
-
method
• B0.03 is used to select the stopping.
• Setting
Setting
Function
constant
0
Ramp to stop
1
Free run stop

5.3.1.4 Prohibiting the reverse rotation : B0.04

Parameter
Name
Unit
No.
Prohibiting
B0.04
-
Reverse Rotation
• B0.04 is used to prohibit the reverse run
• Setting
Setting
Function
constant
0
Reverse rotation enabled
1
Reverse rotation disabled
5. Parameters
5-11
Digit0
Active source of RUN command
in remote mode (0~2)
Setting
Factory
Changeable
range
Setting
during operation
0~1
0
X
Changeable
Setting
Factory
during
range
Setting
operation
0~1
0
X
MOSCON-E7 User's Manual
5-12

5.3.1.5 Setting the motor direction : B0.05

Parameter
Name
Unit
No.
Default Motor
B0.05
-
Direction
• B0.05 is used to select the direction of the motor's rotation
• It is only applicable when B0.02 = 0 (operator)
• Setting
Setting
Function
0
Forward (CCW from the axis view)
1
Reverse (CW from the axis view)
• If B0.04=1, it is automatically changed to 0(forward).

5.3.1.6 Setting the monitor default : B0.06

Parameter
Name
Unit
No.
Default Monitor
B0.06
-
Item
• B0.06 is used to sets the monitor item to be displayed when the power
is turned on.
• If B0.06=5, U0.05 is displayed at power-up.

5.3.1.7 Setting the automatic start operation : B0.07

Parameter
Name
Unit
No.
Automatic start
B0.07
-
after power on
• B0.07 is set to 1, if the motor is to be started automatically at power-up.
• The automatic start option (B0.07=1) is valid only when the active
source of run command is the digital operator. (B0.02=0)
• Setting
Setting
Function
constant
0
Does not use the automatic start operation.
1
Motor runs automatically without RUN command.
Changeable
Setting
Factory
during
range
Setting
operation
0~1
0
O
Changeable
Setting
Factory
during
range
Setting
operation
1~10
0
O
Setting
Factory
Changeable
range
Setting
during operation
0~1
0
O