5.4 F-Parameter

5.4.1 Frequency control functions

5.4.1.1 Setting the frequency/speed command : F0.01~F0.09
Parameter
Name
No.
Main frequency
command of
F0.01
operator mode &
communication
mode
F0.02
Frequency 2~8
~F0.08
F0.09
Jog Frequency
• Parameters F0.01~F0.09 are frequency commands used for multi-step
speed operation as shown in Fig 5.3.
• In multi-step speed operation, JOG command has the top priority.
Thus, when JOG command is on, the frequency command is changed
to F0.09 regardless of terminal status of multi-step speed reference 1~3.
• In keypad mode (B0.01=1) and communication mode (B0.01=3), the
value in F0.01 becomes the active frequency command.
Frequency
reference
Reference 5
Reference 4
Reference 3
F0.03
Reference 2
F0.02
Auxiliary speed
Reference 1
F0.01
RUN/STOP
ON
Multi-step speed reference 1
OFF
ON
Multi-step speed reference 2
OFF
Multi-step speed reference 3
OFF
JOG reference
OFF

Figure 5.3 Timing chart for multi-step and JOG operation

5. Parameters
Changeable
Setting
Factory
Unit
during
range
Setting
operation
0.00
0.01Hz
0.00
O
~600.00
0.00
0.01Hz
0.00
O
~600.00
0.00
0.01Hz
6.00
O
~ 600.00
Reference 8
F0.08
Reference 7
F0.07
Reference 6
F0.06
F0.05
F0.04
JOG frequency
F0.09
OFF
ON
ON
ON
5-15
MOSCON-E7 User's Manual
5-16

5.4.2 Frequency limit

5.4.2.1 Setting lower/upper frequency limit : F1.01,F1.02

Parameter
No.
F1.01
F1.02
• Parameter F1.01 and F2.02 are used to set the upper and lower limit of
output frequency respectively.
• The setting unit of F1.01 and F1.02 is the percentage of the maximum
utput frequency (C0.02).
Frequency Reference
Upper Limit (F1.01)
Frequency Reference
Lower Limit (F1.02)

Figure 5.4 Upper and lower limits of the frequency reference

5.4.3 Jump frequency to avoid mechanical
resonant oscillation

5.4.3.1 Setting jump frequency : F1.03~F1.06

Parameter
No.
F1.03
Jump Frequency1
F1.04
Jump Frequency2
F1.05
Jump Frequency3
F1.06
Setting
Name
Unit
range
High Speed Limit
0.1%
0.1~100.0
Low Speed Limit
0.1%
0~99.9
Internal Frequency Reference
Frequency Command
from User
Setting
Name
Unit
range
0.00
0.01Hz
~600.00
0.00
0.01Hz
~600.00
0.00
0.01Hz
~600.00
Jump Frequency
0.00
0.01Hz
Width
~20.00
Changeable
Factory
during
Setting
operation
100.0
O
0.0
O
Changeable
Factory
during
Setting
operation
0.00
O
0.00
O
0.00
O
0.50
O