Main Circuit Terminal Functions; Control Circuit Terminal Functions; Table 3.1 200V Class Main Circuit Terminal Functions; Table 3.2 400V Class Main Circuit Terminal Functions - Samsung MOSCON-E7 User Manual

Small general-purpose multi-functional inverter
Table of Contents

Advertisement

3.3 Main circuit terminal functions

Table 3.1 200V class main circuit terminal functions

Purpose
Main circuit power input
R/L1, S/L2, T/L3
Inverter outputs
U/T1, V/T2, W/T3
DC power input
+1, N
DC reactor connection
+1, +2 (Remove short-bar)*
Braking unit connection
P/B, N (No internal braking unit)
Auxiliary capacitor
(+): P/B (-):N
Ground
*Short-bar must be removed when connecting the DC reactor.

Table 3.2 400V class main circuit terminal functions

Purpose
Main circuit power input
R/L1, S/L2, T/L3
Inverter output
U/T1, V/T2, W/T3
+2, N (Additional circuit is needed to
DC power input
prevent the damage caused by inrush
current.)
DC reactor connection
+1, +2(Remove short-bar)*
+2, P/B (used for the internal braking
Braking resistor unit
unit)
Braking unit
+2, N
Auxiliary capacitor
(+) : +2 (-) : N
Ground
*Short-bar must be removed when connecting the DC reactor.
3.Wiring
3-7
Symbol
Terminal Symbol
MOSCON-E7 User's Manual
3-8

3.4 Control circuit terminal functions

Table 3.3 Control circuit terminal block
Terminal
Function
1
Forward run/stop command
2
Reverse run/stop command
3
Multi-function input 1
4
Multi-function input 2
5
Multi-function input 3
6
Multi-function input 4
Sequence control input
7
common
8
Power for freq. command
Voltage command for output
9
frequency
Current command for
10
output frequency
11
Analog monitor output
12
Common for control
A1
B1
Multi-function output
C1
Note) Be attentive to below mention when changing output frequency in using the
external frequency command terminal.
- Voltage command input terminal is set only in factory setting.
- Change setting value of parameter H2.01 from 0 to 1 in using the current
command input terminal.
- In setting the function of contact input, H0.02~H0.05, parameter H2.01
is regardless if voltage current command transfer(14) is set.
Signal level
Default setting
-
-
External fault
Photo-Coupler input
+24V, 10mA
Fault reset
Multi-step speed1 command
Jogging command
+24V Ground
Sequence 0V
+12V(Max 20mA)
-
DC 0¡ - +10V(25§ Ù )
-
4¡ - 20mA(250§ Ù )
-
0V
-
DC 0 ¡ -
+10V
(Output frequency)
Contact :
AC 250V, 1A or below
Fault occurred
DC 30V, 1A or below