5.7.3.3 Adjusting analog inputs : H2.03, H2.04, H2.06, H2.07

Parameter
Name
Unit
No.
Voltage Input
H2.03
Gain
0.1%
(Terminal 9)
Voltage Input
H2.04
Bias
0.1%
(Terminal 9)
Current Input
H2.06
Gain
0.1%
(Terminal 10)
Current Input
H2.07
Bias
0.1%
(Terminal 10)
• Adjust gain and bias of analog inputs, as shown in Figure 5.22 if there
are undesirable offset and gain changes in the analog inputs.
• The setting unit of gain and bias changes according to the values in
H2.05. For more details, see the paragraph 5.7.3.4.
Gain
Max. Output Frequency x
100
Bias
Max. Output Frequency x
100
0V
(4mA)
Use the current value in parenthesis
when current input has been selected

Figure 5.22 Gain and Bias

5. Parameters
5-53
Changeable
Setting
Factory
during
range
Setting
operation
0.0
100.0
O
~200.0
-100.0
0.0
O
~100.0
0.0
100.0
O
~200.0
-100.0
0.0
O
~100.0
When H2.05=0
Frequency
Command
Analog input
10V
(20mA)
MOSCON-E7 User's Manual
5-54
5.7.3.4 Setting the multi-function analog input terminal
function : H2.05
Parameter
Name
Unit
No.
Function of
H2.05
Current
-
Input Terminal
• H2.05 is used to set the function of Ain(no. 10) terminal.
• Constants and function for multi-function analog input
• Setting
Setting
Function
constant
0
Frequency command
1
Frequency gain
2
Voltage bias
3
DC breaking current
4
Over torque detection level
Stall prevention level during
5
operation
Minimum frequency command
6
level
7
Jump frequency
Changeable
Setting
Factory
during
range
Setting
operation
0~ 7
0
X
Setting unit is the percentage of
Max. output frequency
Max. output frequency
Max. output voltage
Max. output current
Max. output current
Max. output current
Max. output frequency
Max. output frequency

Advertisement