5.4.4 Frequency match detection

5.4.4.1 Controlling the frequency detection : F1.08. F1.09

Parameter
Name
Unit
No.
Frequency of
F1.08
0.01Hz
Match Detection
Frequency Match
F1.09
0.01Hz
Detection Width
• F1.08 and F1.09 are used to generate the frequency matching signal,
which is used for the operation of multi-function output in section
5.7.2.2. For more details, see section 5.7.2.2.

5.4.4.2 Automatic activation of 2nd accel/decel time : F1.10

Parameter
Name
Unit
No.
Frequency of
F1.10
Accel/Decel Time
0.01Hz
Switching .
• F1.10 is used to automatically activate 2
setting F1.10 other than 0, 2
set of accel/decel times (F2.03 and
nd
F2.04) are automatically applied if the output frequency is higher than
the value specified in F1.10.
Output-Frequency
Acc./Dec. Time
Switching Frequency
(F1.10)
F2-01
F2-03

Figure 5.6 Acceleration/Deceleration time switching frequency

5. Parameters
5-19
Changeable
Setting
Factory
during
range
Setting
operation
0.00
0.00
O
~600.00
0.00
0.50
O
~20.00
Changeable
Setting
Factory
during
range
Setting
operation
0.00
0.00
O
~600.00
set of accel/decel times. By
nd
F2-04
F2-02
MOSCON-E7 User's Manual
5-20
5.4.5 accel/decel time
5.4.5.1 Setting the accel/decel time : F2.01~F2.04
Parameter
Name
Unit
No.
F2.01
AccelTime1
0.01Sec
F2.02
DecelTime1
0.01Sec
F2.03
AccelTime2
0.01Sec
F2.04
DecelTime2
0.01Sec
• Acceleration time: Time required to go up to 100% of the maximum
output frequency from 0%.
• Deceleration time: Time required to go down to 0% of the maximum
output frequency from 100%.
• F2.01~F2.02 can be used to set the acceleration and deceleration time
in normal status.
• F2.03 and F2.04 are activate when :
i) F1.10 > 0 and
ii) Output frequency > F1.10.
• The possible setting ranges for the acce/decel times depends on the
setting in F2.05.
5.4.5.2 Setting the time unit of accel/aecel time : F2.05
Parameter
Name
Unit
No.
Accel/Decel
F2.05
-
Time Base
• F2.05 can be used to set the time base of accel/decel time.
• If F2.05 is set to "1" the setting range will be 0.0 to 6000.0s.
• Setting
Setting
Function
constant
0
Sets the accel/decel time unit to 0.01sec
1
Sets the accel/decel time unit to 0.1sec
Changeable
Setting
Factory
during
range
Setting
operation
0.00
10.00
O
~600.00
0.00
10.00
O
~600.00
0.00
10.00
O
~600.00
0.00
10.00
O
~600.00
Changeable
Setting
Factory
during
range
Setting
operation
0~1
0
X