5.4.6 Configuring S-curve time : F3.01

Parameter
Name
Unit
No.
F3.01
S-Curve time
0.01sec
• F3.01 can be used to set the S-curve pattern time of the accel/decel
changing points to reduce shock caused by abrupt stopping and starting.
ON
Run
Command
Output
Frequency
F 3.01 F 3.01
F 3.01

Figure 5.7 Setting S-curve characteristics

5. Parameters
5-21
Changeable
Setting
Factory
during
range
Setting
operation
0.00~2.50
0.20
O
OFF
F 3.01
Time
MOSCON-E7 User's Manual
5-22

5.5 S-Parameter

5.5.1 DC Braking
5.5.1.1 Controlling DC breaking : S0.01~S0.04
Parameter
Name
Unit
No.
DC Brake
S0.01
Starting
0.01Hz
Frequency
DC Brake
S0.02
1%
Current
DC Braking
S0.03
0.1sec
Time at Start
DC Braking
S0.04
0.1sec
Time at Stop
• S0.01 : The frequency where the DC braking starts.
It is valid only for deceleration.
• S0.02 : The level of output DC current during DC braking.
( in the percentage of rated inverter output current )
• S0.03 : Set the DC braking operation time before the motor is started.
• S0.04 : Set the DC braking operation time before the motor is stopped.
• In order to decrease the stopping time, increase DC braking current in
S0.02.
• To disable the DC braking, set DC braking time (S0.03 and S0.04) to 0.
Run Command
Output
Frequency
C0.07
S0.03

Figure 5.8 DC braking timing chart

Changeable
Setting
Factory
during
range
Setting
operation
0.00 ~10.00
1.50
X
0~ 100
50
X
0.0~ 25.0
0.0
X
0.0~ 25.0
0.5
X
ON
OFF
S0.01
Time
S0.04