5.6 C-Parameter : H/W Functionality setup

5.6.1 V/f Setting
5.6.1.1 Setting V/f : C0.01
Parameter
Name
Unit
No.
C0.01
-
V/f pattern
• C0.01 can be set to one of the following:
- One of 15 preset patterns (settings 0~14)
- A user-programmable pattern (setting 15)
• C0.01 is not changed by initialization (set B1.01= '1010' or '1111').
However, if C0.01=15, C0.02~C0.08 are changed to the values
associated with the case "C0.01=1" by initialization.
• If C0.01=15, the arbitrary V/f pattern can be generated by properly
setting the values in C0.02~C0.08 as shown in Fig 5.14.
• Normally high starting torque is not necessary except the following
cases:
- Long wiring
- Large voltage drop when started
- AC reactor is connected to the input/output of the
inverter
- Running with a motor smaller than the maximum
applicable motor.
- Needs large starting torque (like as in elevator)
• When using preset V/F patterns, consider the rated voltage &
frequency of the motor and load characteristics as shown in the
following table.
5. Parameters
5-31
Changeable
Setting
Factory
during
range
Setting
operation
0~15
15
X
MOSCON-E7 User's Manual
5-32
• Setting
Setting
Max. Frequency
constant
0
50Hz
1
60Hz
2
3
72Hz
4
Square decreased
50Hz
5
6
Square decreased
60Hz
7
8
Smaller starting torque
50Hz
9
Large starting torque
10
Smaller starting torque
60Hz
11
Larger starting torque
12
90Hz
13
120Hz
14
180Hz
Specification
Application
60Hz saturation
General-purpose
50Hz saturation
Fans/Pumps
Cubic decreased
Decreased
torque
Cubic decreased
High start-up
torque
Rated output
operation