Overtorque Detection Level & Overtorque Delay Time : P3.02,P3.03; Fault Retry; Number Of Fault Retry : P4.01; Figure 5.29 Timing Chart For Overtorque Detection - Samsung MOSCON-E7 User Manual

Small general-purpose multi-functional inverter
Table of Contents

Advertisement

P3.02
Motor current
(Output torque)
Overtorque detection1 (NO)
or overtorque detection2 (NO) P3.03
The overtorque detection is cleared when the current drops about
*
5% of the inverter's rated current (or the motor's rated torque)

Figure 5.29 Timing chart for overtorque detection

5.8.4.2 Overtorque detection level & overtorque delay
time : P3.02,P3.03
Parameter
Name
Unit
No.
Overtorque
P3.02
1%
Detection Level
Overtorque
P3.03
1sec
Delay Time
• P3.02 and P3.03 can be used to detect an excessive mechanical load
from an increase in the output current (or output torque)
5. Parameters
5-71
£ ª
5% of the
rated
current
P3.03
ON
ON
Changeable
Setting
Factory
during
range
Setting
operation
0~300
180
O
0.0~10.0
0.1
X
MOSCON-E7 User's Manual
5-72

5.8.5 Fault retry

5.8.5.1 Number of fault retry : P4.01

Parameter
Name
Unit
No.
Number of
P4.01
-
Fault Retry
• P4.01 can be used to restart the inverter automatically even when an
internal fault occurs during inverter operation.
• Use P4.01 only when continuing operation is more important than
possibly damaging the inverter.
• The inverter may be damaged when using the fault retry function
too frequently.
• Since the inverter might be damaged, be sure to take the following
precautions:
- Always set up a molded-case circuit breaker
- Set up a sequence that will stop peripheral equipment when an
inverter fault occurs
• The fault retry function is effective with the following faults.
With others, the protective operation will engage immediately without
attempting to restart operation:
- overcurrent
- motor overload
- inverter overload
- main circuit overvoltage
- main circuit undervoltage
•The counter which counts the number of the past fault is cleared when:
-normal operation is maintained for 10 minutes.
-the fault reset input from digital operator or input terminal is
received after the protection operation.
-the input power supply is off.
Changeable
Setting
Factory
during
range
Setting
operation
0~10
0
X
NOTE