Blocking Logic - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 14
Basic IED functions
InputSelect
AI3P1
AI3P2
GUID-0A8F8AB0-DFA2-4342-9A6F-4B4B436048D3 V1 EN-US
Figure 179: Source Selection Logic
As shown in
AI3P2 input groups to be propagated to the grouped output AI3P (multiplexer functionality). This
output contains both the instantaneous samples and the RMS values of the selected input group.
The outputs AI1, AI2, AI3 and AIN contain instantaneous samples of phase L1, phase L2, phase L3,
and neutral, respectively, of the selected analog input signals group; for example, for direct
connection to the disturbance recorder.
The 3PHSELECT function typically receives inputs from SMAI function block. When either of the
inputs of the corresponding SMAI function block are not connected to an analog channel (either of
the phases is left unconnected), the output of the corresponding unconnected phase is zero. When
one or more inputs are unconnected, the 3PHSELECT function outputs the corresponding sample
and RMS values as zero. When the selected input group is totally unconnected, the 3PHSELECT
function sends the corresponding group outputs as zero.
As InputSelect is setting-groups enabled, it can be changed dynamically during operation based on
system conditions (for example, status of other switches in the substation). This is important, for
example, in a 1½ breakers arrangement, where either side of the middle breaker is potentially the
source side or the load side, to select the appropriate busbar voltage as reference signal.
14.12.6.2

Blocking logic

As the two input signal groups are not necessarily in sync with each other, the 3PHSELECT function
provides the BLOCKOUT output, which is specifically intended to block other application functions
during the time required for re-synchronizing to the respective source. This output goes high for a
user-settable time-period (BlockTime) whenever the InputSelect setting is changed. If InputSelect is
changed again before the BlockTime expires, BLOCKOUT is retriggered so that the output is high for
BlockTime from the latest change of InputSelect.
The input BLKFUNC is used to block all the outputs of the function whenever it is set by the user. All
analog outputs are forced to 0.0 values. The same result is achieved by setting Operation to "Off".
402
Figure
179, the setting InputSelect selects the analog signals from either AI3P1 or
The AI3P1/2 inputs of 3PHSELECT shall be connected only to SMAI, 3PHSUM, or
TRAFOSWT functions. The AI3P output of 3PHSELECT shall be connected only to
ANSGPROC, ACBMSCBR, or TRAFOSWT functions.