Table 184: VMSQI Non group settings (basic)
Name
Operation
3U0DbRepInt
3U0Min
3U0Max
3U0RepTyp
3U0LimHys
3U0AngDbRepInt
U1DbRepInt
U1Min
U1Max
U1RepTyp
U1AngDbRepInt
U2DbRepInt
U2Min
U2Max
U2RepTyp
U2LimHys
U2AngDbRepInt
Table 185: VMSQI Non group settings (advanced)
Name
3U0ZeroDb
3U0HiHiLim
3U0HiLim
3U0LowLim
3U0LowLowLim
U1ZeroDb
U1HiHiLim
U1HiLim
U1LowLim
Table continues on next page
166
Values (Range)
Unit
Off
-
On
1 - 300
Type
0 - 2000000
V
0 - 2000000
V
Cyclic
-
Dead band
Int deadband
0.000 - 100.000
%
1 - 300
Type
1 - 300
Type
0 - 2000000
V
0 - 2000000
V
Cyclic
-
Dead band
Int deadband
1 - 300
Type
1 - 300
Type
0 - 2000000
V
0 - 2000000
V
Cyclic
-
Dead band
Int deadband
0.000 - 100.000
%
1 - 300
Type
Values (Range)
Unit
0 - 100000
m%
0 - 2000000
V
0 - 2000000
V
0 - 2000000
V
0 - 2000000
V
0 - 100000
m%
0 - 2000000
V
0 - 2000000
V
0 - 2000000
V
© 2021 Hitachi Energy. All rights reserved.
Step
Default
-
Off
1
10
1
0
1
318000
-
Dead band
0.001
5.000
1
10
1
10
1
0
1
106000
-
Dead band
1
10
1
10
1
0
1
106000
-
Dead band
0.001
5.000
1
10
Step
Default
1
500
1
288000
1
258000
1
213000
1
198000
1
500
1
96000
1
86000
1
71000
1MRK 511 557-UEN Rev. A
D0E6045T201305151403 v1
Description
Operation Off / On
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Minimum value
Maximum value
Reporting type
Hysteresis value in % of range and is
common for all limits
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Minimum value
Maximum value
Reporting type
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Minimum value
Maximum value
Reporting type
Hysteresis value in % of range and is
common for all limits
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Description
Zero point clamping
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Zero point clamping
High High limit (physical value)
High limit (physical value)
Low limit (physical value)