Signals; Settings - Hitachi Relion 650 Series Technical Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 12
Monitoring
12.1.7.3

Signals

Table 187: VNMMXU Input signals
Name
U3P
Table 188: VNMMXU Output signals
Name
UL1
UL1RANG
UL1ANGL
UL2
UL2RANG
UL2ANGL
UL3
UL3RANG
UL3ANGL
12.1.7.4

Settings

Table 189: VNMMXU Non group settings (basic)
Name
Operation
GlobalBaseSel
UDbRepInt
UMax
URepTyp
ULimHys
UAngDbRepInt
Table 190: VNMMXU Non group settings (advanced)
Name
UZeroDb
UHiHiLim
UHiLim
ULowLim
ULowLowLim
UMin
168
Type
GROUP
SIGNAL
Type
REAL
INTEGER
REAL
REAL
INTEGER
REAL
REAL
INTEGER
REAL
Values (Range)
Unit
Off
-
On
1 - 6
-
1 - 300
Type
0 - 2000000
V
Cyclic
-
Dead band
Int deadband
0.000 - 100.000
%
1 - 300
Type
Values (Range)
Unit
0 - 100000
m%
0 - 2000000
V
0 - 2000000
V
0 - 2000000
V
0 - 2000000
V
0 - 2000000
V
© 2021 Hitachi Energy. All rights reserved.
Default
Description
-
Three phase group signal for voltage inputs
Description
UL1 Amplitude, magnitude of reported value
UL1 Amplitude range
UL1 Angle, magnitude of reported value
UL2 Amplitude, magnitude of reported value
UL2 Amplitude range
UL2 Angle, magnitude of reported value
UL3 Amplitude, magnitude of reported value
UL3 Amplitude range
UL3 Angle, magnitude of reported value
Step
Default
-
Off
1
1
1
10
1
106000
-
Dead band
0.001
5.000
1
10
Step
Default
1
500
1
96000
1
86000
1
71000
1
66000
1
0
1MRK 511 557-UEN Rev. A
D0E6046T201305151403 v1
D0E6048T201305151403 v1
D0E6049T201305151403 v2
Description
Operation Mode On / Off
Selection of one of the Global Base
Value groups
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Maximum value
Reporting type
Hysteresis value in % of range and is
common for all limits
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Description
Zero point clamping in 0,001% of range
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Minimum value
Technical Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Switchsync pwc600